16
ECO-Y INSTALLATION MANUAL
Electrical Data
X13 ECM Motor
Model
Compressor
Model No .
Rated
Voltage
Voltage
Min/Max
Compressor
HWG
Pump
FLA
Ext
Loop
FLA
Blower
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
MCC
RLA
LRA
LRA**
024
ZP20K5E-PFV
208-230/60/1
197/253
21.0
13.5
58.3
21.0
0.4
5.4
4.1
23.4
26.8
40
030
ZP25K5E-PFV
208-230/60/1
197/253
22.0
14.1
73.0
26.0
0.4
5.4
4.1
24.0
27.5
40
036
HRH029U1LP6
208-230/60/1
197/253
27.0
17.3
96.7
34.0
0.4
5.4
4.1
27.2
31.5
45
042
HRH034U1LP6
208-230/60/1
197/253
31.0
20.0
115.0
41.0
0.4
5.4
7.6
33.4
38.4
50
048
HRH040U1LP6
208-230/60/1
197/253
32.0
21.0
115.0
41.0
0.4
5.4
7.6
34.4
39.7
60
060
HRH051U1LP6
208-230/60/1
197/253
41.0
26.3
150.0
53.0
0.4
5.4
7.6
39.7
46.3
70
070
HRH056U1LP6
208-230/60/1
197/253
47.0
30.1
145.0
51.0
0.4
5.4
7.6
43.5
51.0
80
10/20/09
HACR circuit breaker in USA only
** With optional GeoStart
TM
, only available on 208-230/60/1
PSC Motor
Model
Compressor
Model No .
Rated
Voltage
Voltage
Min/Max
Compressor
HWG
Pump
FLA
Ext
Loop
FLA
Blower
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
MCC
RLA
LRA
LRA**
024
ZP20K5E-PFV
208-230/60/1
187/253
21.0
13.5
58.3
21.0
0.4
5.4
1.2
20.5
23.9
35
024*
ZP20K5E-PFV
208-230/60/1
187/253
21.0
13.5
58.3
21.0
0.4
5.4
1.5
20.8
24.2
35
030
ZP25K5E-PFV
208-230/60/1
187/253
22.0
14.1
73.0
26.0
0.4
5.4
1.5
21.4
24.9
35
030*
ZP25K5E-PFV
208-230/60/1
187/253
22.0
14.1
73.0
26.0
0.4
5.4
2.2
22.1
25.6
35
036
HRH029U1LP6
208-230/60/1
187/253
27.0
17.3
96.7
34.0
0.4
5.4
2.2
25.3
29.6
45
042
HRH034U1LP6
208-230/60/1
187/253
31.0
20.0
115.0
41.0
0.4
5.4
3.5
29.3
34.3
50
042*
HRH034U1LP6
208-230/60/1
187/253
31.0
20.0
115.0
41.0
0.4
5.4
4.6
30.4
35.4
50
048
HRH040U1LP6
208-230/60/1
187/253
32.0
21.0
115.0
41.0
0.4
5.4
3.5
30.3
35.6
50
048*
HRH040U1LP6
208-230/60/1
187/253
32.0
21.0
115.0
41.0
0.4
5.4
4.6
31.4
36.7
50
060
HRH051U1LP6
208-230/60/1
187/253
41.0
26.3
150.0
53.0
0.4
5.4
5.9
38.0
44.6
70
070
HRH056U1LP6
208-230/60/1
187/253
47.0
30.1
145.0
51.0
0.4
5.4
5.9
41.8
49.3
70
01/11/10
HACR circuit breaker in USA only
*With optional High-static PSC motor
** With optional GeoStart, only available on 208-230/60/1
High-static option not available on 036, 060, & 070 model sizes.