background image

8

Subject to Technical Modifications of GES Energy Small and GES Energy Medium

Insulation of ducts in heated spaces

Genvex recommends as follows:

Supply and extract ducts:

In warm loft spaces the supply and extract channels must 

be insulated with 50 mm insulation.

Supply and extract air ducts led through heated spaces in 

dwellings do not require insulation. If the supply air duct 

has cooling, bypass or earth heat exchanger installed it 

must be insulated.

Fresh air and exhaust ducts:

In warm loft spaces and warm rooms in dwellings the fresh 

and exthaust air ducts must be insulated with minimum 50 

mm insulation. In addition, the insulation must be covered 

externally with plastic film or aluminium foil in order to 

avoid condensate in the insulation.

We recommend an insulation of 100 mm on the fresh air 

duct when installing a earth heat exchanger.

Refer to your local distributor for guidance on national 

insulation directives.

Reheating of supply air

As the counter current heat exchanger cannot extract all 

the heat from the extract air and supply it to the supply air, 

the supply air will be about 1-4°C colder than the room 

temperature in the dwelling for the whole winter season. 

If this lower supply temperature is insupportable during 

cold periods, a water-based or electrical reheating surface 

can be mounted for reheating the supply air up to room 

temperature.

Water-based reheating surface

To protect the water-based reheating surface from frost 

burst, a frost protection thermostat must be fitted to the unit 

and the surface insulated. The frost protection thermostat 

sensor is mounted behind the fins of the water-based 

reheating surface. The sensor for controlling the motor 

valve is mounted in the supply air channels approx. 500 

mm downstream of the water-based reheating surface 

in order not to be affected by the radiant heat from the 

heating element. The water supply to the water-based 

reheating surface must be executed by an authorised 

plumbing and heating engineer.

Electrical reheating surface

The sensor for controlling the electrical heating surface 

is mounted in the supply air channel approx. 500 mm 

downstream of the electrical reheating surface in order 

not to be affected by the radiant heat from the heating 

element.

Summary of Contents for GES Energy M

Page 1: ...erigesvej 6 DK 6100 Haderslev Tel 45 73 53 27 00 salg genvex dk genvex dk GES ENERGY S GES ENERGY M PASSIVE VENTILATION WITH WIRING DIAGRAM FOR OPTIMA 100 AND OPTI MA 250 INSTALLATION MANUAL UK Versio...

Page 2: ...densate drain 6 Duct system 7 Insulation of ducts in cold loft spaces 7 Insulation of ducts in warm spaces 8 Reheating of supply air 8 Electrical connection 9 Inspection and commissioning of the appli...

Page 3: ...install a thermostat and electrical heater to prevent freezing when the temperature drops below 2 C 7 Air flow adjustments must be made on both supply and exhaust air sides before use of the machine...

Page 4: ...4 Subject to Technical Modifications of GES Energy Small and GES Energy Medium GES Energy 1 Installation The GES Energy 1 is supplied in a vertical version as shown or a horizontal version The vertic...

Page 5: ...n it is necessary to remove the rubber feet and place them on the left site of the unit the bottom A A Visible wall mounts unvisible wall mounts Closet mounting gummif dder som leveret ved vandret mon...

Page 6: ...as an siphon see sketch to the left Use an armed water hose between the drain connecting piece on the unit and the siphon and tightend it in both ends with a collar band From the siphon and to the in...

Page 7: ...ust air Insulation of ducts in cold loft spaces In order to exploit the unit s high recovery potential efficiency it is necessary to insulate the ducts correctly Genvex recommends as follows Supply an...

Page 8: ...om the extract air and supply it to the supply air the supply air will be about 1 4 C colder than the room temperature in the dwelling for the whole winter season If this lower supply temperature is i...

Page 9: ...out 3 Check that filters are clean may be dirty from installation work 4 Check that the condensate drain is correctly mounted with water trap and is protected from freezing Pour 1 litre water into the...

Page 10: ...s Switch the unit off on the switch on the control panel or the switch on the electrical panel Open the front doors and remove the filters When the filters have been cleaned replaced close the front d...

Page 11: ...n off without problems If the condensate drain does not work this could lead to water damage in the dwelling Countercurrent heat exchanger Inspect the countercurrent heat exchanger every year If it is...

Page 12: ...ract air Possible error Faulty extract air fan Clogged extract air fi lter Fuse on the circuit board is blown Cold supply air Possible error Clogged heat changer Faulty extract air fan Clogged extract...

Page 13: ...800W COS 1 H6 R10 Water valve Belimo Bypass 230VAC H7 R10 Fan extract air 230VAC H8 R12 ON OFF Bypass 2x230VAC H9 R10 Fan supply air 230VAC bypass H16 R8 AUX relay 230VAC max 20W H17 R9 AUX relay 230V...

Page 14: ...n Supply air Blue Yellow Water valve EC fan Extract air ON OFF Bypass Brown Brown Blue Blue Yellow green Yellow green Water valve Belimo Bypass Humidity sensor White Red Blue EC fan Supply air Aux rel...

Page 15: ...Fan Supply Max 1 0A EC Fan Exhaust Max 1 0A Mains 1x230VAC 50Hz MAX Fuse 10A Must be connected to earth Yell Green Yell Green Brown Brown Blue Blue Blue Blue Blue Yellow Yellow Yellow Red 5V GND 5V 1...

Page 16: ...16 Subject to Technical Modifications of GES Energy Small and GES Energy Medium...

Page 17: ...imised with the newest technologies Advanced controls ensure that as little energy as possible is used for reaching an optimum level of comfort Today s and future construction place greater and greate...

Reviews: