background image

3 m

1 m

3 m

7

Subject to Technical Modifications of GES Energy Small and GES Energy Medium

Duct insulation, alt. A

Duct insulation, alt. B

Faulty duct insulation

Duct system

It is recommended that the duct system is executed in 

spiral ducting connected with rubber ring seal fittings in 

order to provide a leak-free and durable duct system. 

To achieve a satisfactory low sound level from the unit, 

sound locks must always be fitted to the supply and extract 

duct system between the unit and the first supply and 

extract fittings.

It is recommended that air speeds in the ducts are 

dimensioned at sufficiently low level to prevent noise from 

the supply and extract fittings.

When positioning fresh air and extract roof cowls/grills, 

make sure the two air flows do not intercept, causing 

escaping air to be drawn in again.

It is recommended that grills are placed on the north or 

east side of the house to provide optimum comfort.

Minimum distance: 3 m between supply and exhaust air

Insulation of ducts in cold loft spaces

In order to exploit the unit’s high recovery potential

(efficiency), it is necessary to insulate the ducts correctly.

Genvex recommends as follows:

Supply and extract ducts:

To minimise heat losses from the duct system in cold loft 

spaces, the supply and extract ducts must be insulated 

with a minimum of 100 mm insulation. If insulation form 

alternative A is used, it is recommended that it is executed 

with two layers of 50 mm lamella mats with paper or foil 

externally and with staggered joints between the two 

layers. If the ducts are laid on the rafter foot, alternative B 

may be used. The insulation must always be tightly packed 

round the ducts.

Fresh air and escaping ducts in cold spaces: 

It is recommended that fresh air and escaping ducts 

are insulated with a minimum of 50 mm insulation. The 

fresh air duct is insulated to prevent warm air in the loft in 

summer from heating up the fresh air. Take care to seal the 

termination where the escaping duct is led through the roof 

or through the gable end, in order to avoid condensation 

damage.

Refer to your local distributor for guidance on national 

insulation directives.

Summary of Contents for GES Energy M

Page 1: ...erigesvej 6 DK 6100 Haderslev Tel 45 73 53 27 00 salg genvex dk genvex dk GES ENERGY S GES ENERGY M PASSIVE VENTILATION WITH WIRING DIAGRAM FOR OPTIMA 100 AND OPTI MA 250 INSTALLATION MANUAL UK Versio...

Page 2: ...densate drain 6 Duct system 7 Insulation of ducts in cold loft spaces 7 Insulation of ducts in warm spaces 8 Reheating of supply air 8 Electrical connection 9 Inspection and commissioning of the appli...

Page 3: ...install a thermostat and electrical heater to prevent freezing when the temperature drops below 2 C 7 Air flow adjustments must be made on both supply and exhaust air sides before use of the machine...

Page 4: ...4 Subject to Technical Modifications of GES Energy Small and GES Energy Medium GES Energy 1 Installation The GES Energy 1 is supplied in a vertical version as shown or a horizontal version The vertic...

Page 5: ...n it is necessary to remove the rubber feet and place them on the left site of the unit the bottom A A Visible wall mounts unvisible wall mounts Closet mounting gummif dder som leveret ved vandret mon...

Page 6: ...as an siphon see sketch to the left Use an armed water hose between the drain connecting piece on the unit and the siphon and tightend it in both ends with a collar band From the siphon and to the in...

Page 7: ...ust air Insulation of ducts in cold loft spaces In order to exploit the unit s high recovery potential efficiency it is necessary to insulate the ducts correctly Genvex recommends as follows Supply an...

Page 8: ...om the extract air and supply it to the supply air the supply air will be about 1 4 C colder than the room temperature in the dwelling for the whole winter season If this lower supply temperature is i...

Page 9: ...out 3 Check that filters are clean may be dirty from installation work 4 Check that the condensate drain is correctly mounted with water trap and is protected from freezing Pour 1 litre water into the...

Page 10: ...s Switch the unit off on the switch on the control panel or the switch on the electrical panel Open the front doors and remove the filters When the filters have been cleaned replaced close the front d...

Page 11: ...n off without problems If the condensate drain does not work this could lead to water damage in the dwelling Countercurrent heat exchanger Inspect the countercurrent heat exchanger every year If it is...

Page 12: ...ract air Possible error Faulty extract air fan Clogged extract air fi lter Fuse on the circuit board is blown Cold supply air Possible error Clogged heat changer Faulty extract air fan Clogged extract...

Page 13: ...800W COS 1 H6 R10 Water valve Belimo Bypass 230VAC H7 R10 Fan extract air 230VAC H8 R12 ON OFF Bypass 2x230VAC H9 R10 Fan supply air 230VAC bypass H16 R8 AUX relay 230VAC max 20W H17 R9 AUX relay 230V...

Page 14: ...n Supply air Blue Yellow Water valve EC fan Extract air ON OFF Bypass Brown Brown Blue Blue Yellow green Yellow green Water valve Belimo Bypass Humidity sensor White Red Blue EC fan Supply air Aux rel...

Page 15: ...Fan Supply Max 1 0A EC Fan Exhaust Max 1 0A Mains 1x230VAC 50Hz MAX Fuse 10A Must be connected to earth Yell Green Yell Green Brown Brown Blue Blue Blue Blue Blue Yellow Yellow Yellow Red 5V GND 5V 1...

Page 16: ...16 Subject to Technical Modifications of GES Energy Small and GES Energy Medium...

Page 17: ...imised with the newest technologies Advanced controls ensure that as little energy as possible is used for reaching an optimum level of comfort Today s and future construction place greater and greate...

Reviews: