When installing the GES Energy follow these instructions:
1) Turn off the electricity before opening the unit
2) Install an air tight water trap on a non-freezing location to
compensate for the fan pressure.
3) The height of the water trap
must be
at least 50 mm.
4) Make sure that the drain flows downwards all the way
from the unit.
5) Pour 1 liter water into the drip tray of the unit to verify that
it is drained properly. Before each heating season make
sure that the drain is filled with water.
6) If freezing of the water trap occurs, it is necessary to
install a thermostat and electrical heater to prevent
freezing when the temperature drops below +2 C°.
7) Air flow adjustments must be made on both supply
and exhaust air sides before use of the machine. It is
important supply and exhaust air volumes are balanced.
8) It is recommended to keep the ducts closed until the unit
is started and the system is adjusted.
This instruction must be followed. If the condensate drain
is not made according to this instruction, GENVEX A/S can
not be made responsible for any additional damages, which
have nothing to do with the GENVEX unit.
.