background image

 

  

13

Electrical installation

ECO 275 is equipped for the external connection of 230 

volt power plug, internet, display, BMS connection and 

Genvex accessories.

See wiring diagrams and operating instructions for the 

Optima 270 for more information.

In general, all electrical connections to the ECO 275 must 

be made by an authorised professional.

Important!!

For functional and safety reasons, the unit must be con-

nected to a socket with grounding matched to the plug 

connection.

Control and calibration of the system

To achieve optimal operation of the system, it must be 

calibrated using specialist ventilation measuring equip-

ment. If it is desired to put the system into operation 

before calibration, the following approach can be taken:

Before putting the system into operation

1. Check that the Genvex unit is correctly mounted and that 

all the ducts are properly insulated.

2. Check that the door can be opened so that it is possible 

to service and maintain the unit.

3. Check that the filters are clean (they may be dirty after 

installation).

4. Set all supply air valves so that the valve closest to the 

unit is opened 3 turns from the closed position and the 

outer one is opened 8 turns from the closed position. The 

intermediate valves are opened between 4 and 7 turns, 

depending on how close they are to the unit.

The system can now be put into operation and run until the 

system is calibrated using specialist ventilation measuring 

equipment.

Optimal initial calibration of the system

Genvex recommends that the ventilation unit should be 

calibrated by an authorised Genvex dealer before it is put 

into operation.

Before starting the initial calibration, check that the 4 

points in the section on control and calibration of the 

system have been performed. Then start the unit:

Set the initial basic ventilation value, which is speed 2. To 

reduce energy consumption as much as possible, first 

adjust the main air flows to the desired air flow by adjusting 

the speed of the fans via the control panel.

Then adjust the supply air and exhaust air valves with air 

measuring equipment (during the initial calibration of the 

valves, remember to lock them and to turn the baffle plate 

in the supply air valves so that the air blows in the right 

direction).

Check the main air volumes again and fine-tune the main air 

volumes using the outdoor air and exhaust air valves (being 

sure to lock the position of the valves after the initial 

adjustment).

Summary of Contents for ECO 275

Page 1: ...ECO 275 Mechanical ventilation with passive heat recovery A INSTALLATION MANUAL...

Page 2: ...Control and calibration of the system 13 Optimal initial calibration of the system 13 System maintenance 14 Filters 14 Access to internal parts 15 Preheating surface 16 Fan 16 Supply air and exhaust a...

Page 3: ...eived guidance on using the appliance in a safe way and under stand the dangers involved Children must not play with the appliance Cleaning and user maintenance must not be performed by children witho...

Page 4: ...ulating preheater can be selected for the system which ensures that balanced air volumes can be maintained even during periods of very cold outdoor temperatures An integrated water level switch can al...

Page 5: ...to the location of living spaces As this is a technical product that contains fans and or a heat pump in rare cases and in combination with inappropriate installation conditions it may cause unsatisf...

Page 6: ...veksler 6 Udsugningsventilator 7 Indbl sningsventilator 8 Filter udsugningsluft 9 Filter friskluft 10 Print 11 Bypass 12 Kondensafl b 13 Ekstern el tilslutning M lskitse H jre model M l i mm 1 Frisklu...

Page 7: ...2 13 8 6 60 A 1 3 A 558 141 276 131 260 131 296 60 1118 1071 290 570 160 200 38 4 3 1 2 5 7 9 11 10 12 13 8 6 1 Outdoor air 2 Extract air 3 Exhaust air 4 Supply air 5 Heat exchanger 6 Supply air fan 7...

Page 8: ...water level switch For more details on conversion contact your Genvex sales representative Duct connection top bottom only for ECO 275 light ECO 275 light can be delivered with a supply air connection...

Page 9: ...t installation it is recommended to use 4 x 160 mm nipple connectors with double sealing lips Alternatively a 200 mm spiro pipe can be used that must be connected directly to the outside of the ECO 27...

Page 10: ...lation it is necessary to install a thermostatically controlled heating wire around the condensate drain During operation the unit experiences internal negative pressure Therefore it is necessary to e...

Page 11: ...he house to achieve optimal comfort in houses apartments It is recommended that the air intake should be located on the north or east side of the house to achieve maximum comfort and minimal impact fr...

Page 12: ...heating the fresh air in the summer Be sure to seal the connection where the outgoing duct passes through the roof or gable to prevent condensation damage Insulation of ducts in heated rooms Genvex r...

Page 13: ...turns from the closed position and the outer one is opened 8 turns from the closed position The intermediate valves are opened between 4 and 7 turns depending on how close they are to the unit The sys...

Page 14: ...ht in Optima Basic This means that the filters must be replaced cleaned Stop the system by removing the device plug in ECO 275 or at the socket Open the filter plugs and remove the filters Once the fi...

Page 15: ...internal parts 2 Remove the bracket with the sensor mounted in the exchanger 3 Disassemble the exchanger by pulling on the belt gently 4 Remove the fan housing and if included built in prehea ting sur...

Page 16: ...nd exhaust air valves Clean the valves by wiping them with a dry cloth Make sure that the valve does not rotate thus causing a change in the air volume Important When reinstalling the front plate on t...

Page 17: ...ean with water 12 months Gaskets in general Check gaskets on the unit and make sure they are intact 12 months Supply air and exhaust air valves Check for dirt inside the supply air and exhaust air val...

Page 18: ...2014 Counterflow exchanger 400 mm 23 069807 Sensor clips for exhaust air 24 072024 Gasket for counterflow exchang er 25 072040 Blind plug M25x1 5 26 072021 Bottom plate Ral 9016 27 072046 Sealing stri...

Page 19: ...e system No supply air Defective supply air fan Clogged supply air filter Outdoor air grille clogged with dirt and leaves during autumn or snow and ice during winter Fuse on control board has blown Un...

Page 20: ...t Sensor T7 Extract air Sensor T4 Exhaust air Sensor T3 Outdoor air Sensor T1 Supply air Sensor T9 Option External stop EC fan Extract air Blue Yellow EC fan Supply air Blue Yellow EC fan Extract air...

Page 21: ...Sensor T7 Extract air Sensor T4 Exhaust air Sensor T3 Outdoor air Sensor T1 Supply air Sensor T9 Option External stop EC fan Extract air Blue Yellow EC fan Supply air Blue Yellow EC fan Extract air 1...

Page 22: ...22 DECLARATION OF CONFORMITY The declaration of conformity can be found on our website www genvex com...

Page 23: ...23 DE INSTALLATION INSTRUCTIONS For further information on dismantling components with a view to disposal and recycling see illustrations under System maintenance...

Page 24: ...ilies At the same time our system is an important element when it comes to saving energy in homes and in society as a whole in fact you can recover up to 95 of the heat energy with a Genvex system All...

Reviews: