GE-VX INSTALLATION
GE-VX
Section B-12
Powering Up Procedure
Verify all Connections
Once the GE-VX is properly mounted on the wall and all modules to the terminal block,
perform the following steps:
-
Ensure the flat cable between the bottom electronic board and the faceplate electronic
board is properly connected.
-
Seal all cable entry holes.
Hermetically Close the GE-VX
Close the front panel and the lower access cover.
Put the power on
Secure the front panel with a lock
Specifications
Module GE-V1 and GE-V2
DESCRIPTION
VALUE
Storage temperature
-4°F to 131°F (-20°C to 55°C)
Operating temperature
32°F to 122°F (0°C to 50°C)
Humidity
90% maximum Non-condensing
Weight
2 lb (0.9Kg)
Size
12 1/4” x 11” x 4 3/4” (32 cm x 28.8 cm x
11.5 cm)
Norms
CSA (NRTL/C)
Protection index
IP 54 (dust and splashing water)
Warranty
2 years
VARIABLE OUTPUT
Fuse for output 1 and 2
15 A @ 250 VAC
Maximum load for output 1 and 2
The current shall not exceed 12.5A at each
output (OUT 1-2) for a resistive load. For an
inductive load, the current shall not exceed 10A
at each output (OUT 1-2).
Important Notice.
-
Low-voltage and high-voltage wire must be passed through different conducts at
least 1 foot (30 cm) apart. If low-voltage and high-voltage conduits must be
crossed, the crossing must be at a 90-degree angle.
-
All wiring must be made by a certified electrician and conform to local electrical
regulations.
www.monitrol.com