14

Fig. 3

ENGLISH

8  MEMORY STORING THE RADIO CODE

The control board has an integrated 2-channel decoding 
system. This system makes it possible to memory-store both 
total opening (OPEN A) and partial opening OPEN B) of the 
automated system - this is made possible by an additional 
receiver module (fig.3 ref. 

) and radio controls on the same 

frequency. 

 Only one radio code can be used at a time.

To change over from one code to another, you 

must delete the existing one (see paragraph 

on deletion), and repeat the memory-storage 

procedure.

8.1  MEMORY STORAGE OF 868 RADIO CONTROLS

 A maximum of 250 codes can be memory 

stored, split between OPEN A and OPEN B.

On the radio control, simultaneously press and hold down 
push-buttons P1 and P2.
The radio control LED begins to flash.
Release both push-buttons.
Press the LOGIC (SW3) or SPEED (SW2) push-button, to 
memory store respectively total opening (OPEN A) or partial 
opening (OPEN B), and as you hold it down, also press the 
SETUP (SW1) push-button. The relevant LED starts to flash 
slowly for 5 sec.
Release both push-buttons.
Within these 5 sec., while the radio control LED is still flashing, 
press and hold down the required push-button on the radio 
control (the radio control LED lights up on steady beam).
The LED on the board lights up on steady beam for 1 
second and then goes OFF, indicating that storage was 
executed.
Release the radio control push-button.
Quickly press twice the memory stored radio control push-
button.

  The automated system performs one opening 

operation. Make sure that the automated 

system is free of any obstacle created by 

persons or things.

To add other radio controls, transfer the code of the memory-
stored push-button of the radio control to the relevant push-
button of the radio controls to be added, observing the 
following procedure.

On the memory stored radio control, simultaneously press 
and hold down push-buttons P1 and P2.
The radio control LED begins to flash.
Release both push-buttons.
Press the memory stored push-button and hold it down 
(the radio control LED lights up on steady beam).
Bring the radio controls near, press and hold down the 

1.

2.
3.
4.

5.
6.

7.

8.
9.



7.2  MEMORY STORAGE  OF BUS ACCESSORIES

You can add the BUS photocells to the system at any time, 
simply by memory-storing them on the board, observing the 
following procedure:

Install and program the accessories using the required 
address (see paragraph 7.1)
Cut power to the board.
Connect the two accessories cables to the red terminal-
board J10 (any polarity will do).
Power up the board, taking care to first connect the 
main power supply (transformer output) and then any 
batteries.
Quickly press once only the SW1 (SETUP) push-button, to 
execute learning. The BUS LED flashes.
Give an OPEN A impulse, leaves will move and the BUS 
learning procedure is over.

The board has memory stored the BUS accessories. Follow the 
instructions in the table below to check if the BUS connection 
is correct.

Tab. 4 - Description of BUS LED

Steady light

Normal operation (LED ON even in the 
absence of photocells)

Slow flashing 
lamp 

(flash 

every 0.5 sec)

At least one input engaged: photocell 
engaged or not aligned, Open A or Open 
B or Stop input engaged

Light OFF

(flash every 2.5 
sec)

BUS line short circuited

Fast flashing 
lamp 

(flash 

every 0.2 sec)

If you have detected a BUS connection 
error, repeat the acquisition procedure. If 
the error is repeated, make sure that there 
is not more than one accessory with the 
same address in the system (also see the 
accessories instructions)

1.

2.
3.

4.

5.

6.

Summary of Contents for BRAIN 06 24V

Page 1: ...BRAIN 06 24V...

Page 2: ...5 The automated system is supplied with an intrinsic anti crushing safety device con sisting of a torque control Nevertheless its tripping threshold must be checked as specified in the Standards indic...

Page 3: ...ccessiva modifica 92 31 CEE e 93 68 CEE Nota aggiuntiva Questo prodotto stato sottoposto a test in una configurazione tipica omogenea tutti prodotti di costruzione GENIUS S p A Grassobbio 01 09 2006 L...

Page 4: ...ianto un interruttore magnetotermico differenziale con adeguata soglia di intervento Separare sempre i cavi di alimentazione da quelli di comando e di sicurezza pulsante ricevente fotocellule ecc Per...

Page 5: ...LEDs di segnalazione Morsetto e o Morsettiera Descrizione Dispositivo collegato 1 J5 24V Alimentazione ac cessori 2 GND Negativo 3 3 STOP STOP Dispositivo con Dispositivo con contatto N C che contatt...

Page 6: ...di prelampeggio in seguito a un comando di OPEN l apparecchiatura attiva il lampeggiatore per 3 secondi prima di iniziare il movimento agendo come di seguito descritto Premere per almeno 5 sec il tast...

Page 7: ...cevitore delle fo tocellule BUS della battuta meccanica di apertura Se stata impostata la forza BASSA attendere circa 5 sec verificando lo spegnimento del lampeggiante Nel caso sia selezionata la logi...

Page 8: ...da aggiungere seguendo la seguente procedura Sul radiocomando memorizzato premere e tenere pre muti i pulsanti P1 e P2 contemporaneamente Il led del radiocomando inizier a lampeggiare Lasciare entram...

Page 9: ...ato Procurarsi un radiocomando gi memorizzato su uno dei 2 canali OPEN A o OPEN B Premere e tenere premuti i pulsanti P1 e P2 contempora neamente fino a quando entrambi i led lampeggeranno lentamente...

Page 10: ...apre le ante 1 Se il ciclo iniziato con un OPEN B apertura parziale un impulso di OPEN A aziona entrambe le anta in aper tura 11 TABELLE DELLE LOGICHE LOGICA A IMPULSI STATO AUTOMAZIONE OPEN A OPEN B...

Page 11: ...C and subsequent amendment 92 31 EEC and 93 68 EEC Additional information This product underwent a test in a typical uniform configuration all products made by GENIUS S p A Grassobbio 01 09 2006 The M...

Page 12: ...system a differential thermal breaker with adequate tripping threshold Always separate power cables from control and safety cables push button receiver photocells etc To avoid any electrical disturban...

Page 13: ...es protective fuse F2 Fuses protecting transformers and motors LED Signalling LEDs 3 1 DESCRIPTION OF COMPONENTS Terminal and or terminal board Description Device connected 1 J5 24V Power supply for a...

Page 14: ...inputs the closed at rest automated system condition is shown in bold Check the status of the signalling LEDs as per table below Tab 1 Operation of inputs status LEDs 6 4 2 MANUAL SET UP To execute a...

Page 15: ...shows the programming operations of the dip switch inside the transmitter and of the BUS Photocells receiver If the A Logic was selected the board begins to count the pause time max 10 min and after...

Page 16: ...the memory stored push button of the radio control to the relevant push button of the radio controls to be added observing the following procedure On the memory stored radio control simultaneously pre...

Page 17: ...ROLS A maximum of 250 codes can be memory stored split between OPEN A and OPEN B Use 433 remote controls only with receiver module at 433 MHz Press the LOGIC SW3 or SPEED SW2 push button to memory sto...

Page 18: ...g and closing inhibited opens leaves 1 If the cycle began with OPEN B partial opening an OPEN A pulse will activate both leaves to open LOGIC A PULSES STATUS OF AUTOMATED SYSTEM OPEN A OPEN B STOP FSW...

Page 19: ...92 31 CEE et 93 68 CEE successives Note compl mentaire Ce produit a t test dans une configuration typique homog ne tous les produits sont fabriqu s par GENIUS S p A Grassobbio le 01 09 2006 L Adminis...

Page 20: ...cteur magn tothermique diff rentiel au seuil d intervention ad quat Toujours s parer les c bles d alimentation des c bles de commande et de s curit bouton poussoir r cepteur photocellules etc Pour vit...

Page 21: ...ransformateur et moteurs LED LEDs de signalisation 3 1 DESCRIPTION DES COMPOSANTS Borne et ou Bornier Description Dispositif connect 1 J5 24V Alimentation accessoires 2 GND N gatif 3 3 STOP STOP Dispo...

Page 22: ...es retards de vantail en ouverture et fermeture et le temps pause 30s avec logique A sont pr s lectionn s par la platine et on ne peut pas les modifier 1 2 3 4 5 6 7 8 9 10 6 4 2 SETUP MANUEL Pour ex...

Page 23: ...a programm la force BASSE attendre environ 5 s en v rifiant l extinction de la lampe clignotante Si l on a s lectionn la logique A la platine commence le comptage du temps de pause 10 min maxi et apr...

Page 24: ...mandes transf rer le code du bouton poussoir de la radiocommande m moris e vers le bouton poussoir correspondant des radiocommandes ajouter en proc dant comme suit Sur la radiocommande m moris e appuy...

Page 25: ...maxi 250 codes r partis entre OPEN A et OPEN B N utiliser les t l commandes 433 qu avec le module r cepteur 433 MHz Appuyer sur le bouton poussoir LOGIC SW3 ou SPEED SW2 pour m moriser respectivement...

Page 26: ...re inhib es ouvre les vantaux 1 Si le cycle a commenc avec OPEN B vantail d gag une impulsion d OPEN A actionne les deux vantaux en ouverture LOGIQUE A IMPULSIONS TAT AUTOMATISME OPEN A OPEN B STOP FS...

Page 27: ...Este producto ha sido sometido a pruebas en una configuraci n t pica homog nea todos los productos son de fabricaci n GENIUS S p A Grassobbio 01 09 2006 El Administrador Delegado D Gianantoni NDICE 1...

Page 28: ...n un interruptor magnetot rmico diferencial con un adecuado umbral de intervenci n Separe siempre los cables de alimentaci n de los cables de mando y de seguridad pulsador receptor fotoc lulas etc Pa...

Page 29: ...ible protecci n transformador y motores DIODO DIODOS de se alizaci n 3 1 DESCRIPCI N DE LOS COMPONENTES Borne y o Regleta de bornes Descripci n Dispositivo conectado 1 J5 24V Alimentaci n accesorios 2...

Page 30: ...taci n de los motores Con el SETUP AUTOM TICO los espacios de deceleraci n los retardos de hoja en apertura y cierre y el tiempo de pausa 30 seg con l gica A est n prefijados por la tarjeta y no se pu...

Page 31: ...lulas BUS En la fig 2 se muestra una automaci n batiente de dos hojas donde se indican los haces de alcance de las fotoc lulas A Fotoc lulas con intervenci n en APERTURA y CIERRE B Fotoc lulas con int...

Page 32: ...llo proceda del siguiente modo En el radiomando memorizado presione y mantenga presionados los pulsadores P1 y P2 simult neamente El diodo del radiomando empezar a destellar Suelte ambos pulsadores Pr...

Page 33: ...ulo receptor a 433 MHz Presione el pulsador LOGIC SW3 o SPEED SW2 para memorizar respectivamente la apertura total OPEN A o la parcial OPEN B manteniendo el pulsador presionado presione tambi n el pul...

Page 34: ...ibidos Abre las hojas 1 Si el ciclo ha iniciado con OPEN B hoja libre un impulso de OPEN A acciona ambas hojas en apertura L GICA A IMPULSOS ESTADO DE LA AUTOMACI N OPEN A OPEN B STOP FSW OP FSW CL FS...

Page 35: ...n aufzubewahren Mit dem Symbol sind wichtige Anmerkungen f r die Sicherheit der Personen und den st rungsfreien Betrieb der Automation gekennzeichnet Mit dem Symbol wird auf Anmerkungen zu den Eigensc...

Page 36: ...tzschalter mit entsprechender Ausl seschwelle einbauen Die Versorgungskabel stets von den Steuer und Sicherheitskabeln Taste Empf nger Fotozellen usw trennen Um jegliche elektrische St rung zu vermeid...

Page 37: ...kann jederzeit durch Dr cken der Taste SW3 ausgew hlt werden Die ausgew hlte Betriebslogik wird dann durch die LED LD7 angezeigt LED ein Logik AUTOMATISCHER A LED aus Logik HALBAUTOMATISCHER SCHRITTBE...

Page 38: ...gerungen des Fl gels beim ffnen und beim Schlie en sowie die Pausenzeit 30 Sek Logik A von der Karte vorgegeben und k nnen nicht ge ndert werden 1 2 3 4 5 6 7 8 9 10 6 4 2 MANUELLES SETUP F r das MANU...

Page 39: ...b 2 In der Abb 2 ist eine Automation f r ein Fl geltor mit 2 Fl geln und der Angabe der Deckungsbereiche der Fotozellen dargestellt A Fotozellen mit Ausl sung beim FFNEN und beim SCHLIESSEN B Fotozell...

Page 40: ...e Tasten P1 und P2 gleichzeitig anhaltend dr cken Die LED der Funksteuerung blinkt Beide Tasten loslassen Die eingespeicherte Taste anhaltend dr cken die LED der Funksteuerung leuchtet mit Dauerlicht...

Page 41: ...dul zu 433 MHz verwenden Die Taste LOGIC SW3 oder SPEED SW2 dr cken um jeweils die vollst ndige ffnung OPEN A bzw die Teil ffnung OPEN B einzuspeichern und dabei auch die Taste SETUP SW1 gedr ckt halt...

Page 42: ...ffnet die Fl gel 1 Wurde der Zyklus mit OPEN B Fl gel entblockt begonnen werden mit einem Impuls OPEN A beide Fl gel in der ffnung gesteuert LOGIK A IMPULSE STATUS DER AUTOMATION OPEN A OPEN B STOP FS...

Page 43: ...ke opmerkingen voor de veiligheid van personen en om het automatische systeem in goede staat te houden Het symbool vestigt de aandacht op opmerkingen over de eigenschappen of de werking van het produc...

Page 44: ...hermische differentieelschakelaar is gemonteerd met een geschikte inschakellimiet Houd de voedingskabels altijd gescheiden van de kabels voor de bediening en de beveiliging drukknop ontvanger fotocell...

Page 45: ...elk willekeurig moment worden geselecteerd door op de knop SW3 te drukken De geselecteerde logica wordt vervolgens weergegeven door de led LD7 LED aan logica AUTOMATISCH A LED uit logica HALFAUTOMATIS...

Page 46: ...n de vertragingsruimte de vertragingen van de vleugel bij het openen en sluiten en de pauzetijd 30 sec met A logica reeds vastgelegd door de kaart en kunnen niet worden gewijzigd 1 2 3 4 5 6 7 8 9 10...

Page 47: ...fig 2 is een automatisch systeem weergegeven met 2 vleugels met aanduiding van het bereik van de fotocellen A Fotocellen die ingrijpen tijdens OPENING en SLUITING B Fotocellen die ingrijpen tijdens O...

Page 48: ...e toe te voegen afstandsbedieningen volgens de volgende procedure Druk op de in het geheugen opgeslagen afstandsbediening de knoppen P1 en P2 in en houd ze tegelijkertijd ingedrukt De led van de afsta...

Page 49: ...sbedieningen uitsluitend met de 433 MHz ontvangstmodule Druk op de LOGIC knop SW3 of de SPEED knop SW2 om respectievelijk de volledige opening OPEN A of de gedeeltelijke opening OPEN B in het geheugen...

Page 50: ...Als de cyclus begonnen is met OPEN B n vleugel drijft een OPEN A impuls beide vleugels aan met een openende beweging LOGICA A IMPULSEN STATUS AUTOMATISCH SYSTEEM OPEN A OPEN B STOP FSW OP FSW CL FSW...

Page 51: ...rgaben der unter Punkt 10 an gegebenen Vorschriften zu berpr fen 16 Die Sicherheitsvorrichtungen Norm EN 12978 erm glichen den Schutz eventueller Gefahrenbereiche vor mechanischen Bewegungsrisiken wie...

Page 52: ...ht vor ohne die wesentlichen Eigenschaften dieses Ger tes zu ver ndern und ohne Verbindlichkeiten in Bezug auf die Neufassung der vorliegenden Anleitungen technisch bzw konstruktiv kommerziell bedingt...

Reviews: