![Genetec Synergis IX SY-SIX-RDM2-DIN-485 Installation Manual Download Page 19](http://html1.mh-extra.com/html/genetec/synergis-ix-sy-six-rdm2-din-485/synergis-ix-sy-six-rdm2-din-485_installation-manual_2211532019.webp)
SY-SIX-RDM2-DIN-485 | Synergis IX DIN Rail 2 Door Expander | Installation Manual
Last Updated September 2018
19
Outputs
The Reader Expander has 8 Programmable Outputs (PGMs). These outputs are used to activate bell sirens,
lighting circuits, door locks, relay accessory products and other automation points.
Lock PGM Outputs (1 and 2)
Relays are provided on PGM output 1 and 2 these are used for the Lock 1 (PGM1 RD001:01) and Lock2
(PGM2 RD001:02) functions and are used to control electric door strikes and other lock control devices. The
lock relay will switch a maximum current of 7A resistive.
Lock Output PGM1/2 Connection (PGM 1 Shown):
+
-
1N4007 Diode
12VDC Electric
Locking Device
+
-
Power Supply for
Locking Devices
Max 30VDC
V+
V-
NO
C
N
C
N
O
C
NC