background image

 

 

1.  With  the  ohmmeter  set  on  its  lowest  scale  take  a 

reading  between  the  top  center  contact  of  the  cell 
and the ionizing fingers on the bottom of the cell. You 
should  have  continuity.  If  you  do  not  then  there  is  a 
bad  contact  between  the  center  contact  and  the  top 
set of ionizing fingers. 

2.  Test  the  resistance  between  the  top  center  contact 

and  the  cell  frame.  You  should  read  infinite 
resistance.  If  not  you  have  a  short  in  the  ionizing 
section. 

3.  Take a reading between the two outside contacts on 

the top of the cell. You should have continuity. If you 
do not then there is a bad contact between one of the 
contacts  to  the  live  cell  plate.  Test  each  top  outside 
contact to the last plate in the cell to determine which 
contact is not mating properly. 

4.  Test the resistance between the outside contacts and 

the  cell  frame. You  should  read  infinite resistance. If 
not you have a short in the collecting section. 

5.  If you have a bad contact adjust the internal contacts 

within the cell until contact is made. 

 

Removing Power Box 

1.  Turn  the  main  system  switch 

OFF

  or  disconnect  the 

power cord. 

2.  Remove the power box cover. 
3.  If  the  unit  does  not  have  a  cord  disconnect  the 

source wires to the Air Cleaner. Cap off the wires so 

the system can still be operated. 

4.  Remove  the  two  nuts  holding  the  power  box  to  the 

cabinet.  

5.  Slide  the  power  box  forward  then  up  to  remove  it 

from the cabinet. 

6.  If  you  are  removing  the  power  box  for  any  length  of 

time tape a cover over the top opening to prevent air 
from entering into the system. 

 

Replacing A Tungsten Ionizing Wire 

Replacement  wires  are  cut  to  the  correct  length  and 

have eyelets at each end for easy replacement. 
1.  Turn 

OFF

 power to Air Cleaner. 

2.  Remove cell from Air Cleaner. 
3.  Remove  all  parts  of  broken  wire  from  the  cell.  If 

necessary, the cell may be used temporarily with one 
wire missing until a replacement is received. 

4.  Place  one  end  of  the  loop  over  the  finger  at  the 

bottom of the cell.  

5.  Using needle-nose pliers, grip the other end of  wire, 

near  the  bottom  of  the  top  loop.  Pull  the  wire  up 
toward  the  top  finger.  As  you  apply  tension,  the 
bottom finger will give, allowing the placement of the 
loop around the top finger. 

6.  Install cell in Air Cleaner. 
7.  Return power to Air Cleaner. 
8.  Test cell for proper operation. 

10 

Fig. 7 

 Exploded View 

Use Part Numbers When Ordering (See next page) 

Part Description 

On/Off Switch 

Safety Interlock Switch 

Performance Indicator Light (Green LED) 

Air Proving Switch 

24 Volt Transformer 

Power Board 

Fibreboard (with 4 Copper Contacts) 

Copper Contact 

Cord Assembly (Optional) 

10 

Cover for Power Box 

11 

Power Box Complete (No Cover) 

12 

Carbon Filters (Set of 3) 

13 

Prefilter 

14 

Cell Guide (Plastic) 

15 

Collecting Cell 

16 

Cell Handle 

17 

Door (with Plastic Clip & Handle) 

18 

Door Handle (Plastic) 

19 

Ionizing Wire 

20 

Male & Female Door Clip Set 

21 

Door Label (Important… Wait 15 Seconds)

 

22 

Door Label (Cleaning Instructions) 

23 

Dax Detergent 

Summary of Contents for GA50A14

Page 1: ...gi bacteria viruses and more down to 0 01 micron Light Weight Aluminum Collecting Cells are durable and easy to maintain Cell Guide ensures proper placement of collecting cells Activated Carbon Filter...

Page 2: ...le of electrostatic precipitation Millions of airborne pollutants are carried through the return air ducts of the heating cooling system and treated through four stages of filtration The prefilters 2...

Page 3: ...same time INSTALLATION Static Pressure The static pressure drop across the Air Cleaner will vary with CFM and whether the optional carbon filters have been installed in the unit Location The Air Clean...

Page 4: ...ner If the atomizing type humidifier is installed upstream high humidity salts and minerals may decrease the efficiency of the collecting cells and cause service problems If the atomizing type humidif...

Page 5: ...ent direction than the left to right set up The handle should face the door Close access door Wiring Wiring should only be performed by qualified personnel only All wiring must comply with all applica...

Page 6: ...ith DAX Detergent or a non chlorine non corrosive non abrasive liquid household detergent Allow detergent to run down both sides of plates and ionizing wires Let stand for 5 minutes or fill up laundry...

Page 7: ...age from the power board Measuring High Voltage At Power Board A high voltage meter capable of measuring up to 10 000 VDC is required to test the voltage 1 The Air Cleaner should be ON with the cells...

Page 8: ...oard is turned on and the performance light will come on The light on the power switch will be lit even when the APS is open If the power board fails to come on with the fan on check that the sensor i...

Page 9: ...Cleaner 8 Remove the high voltage meter 9 Replace the power box cover 10 Turn ON the Air Cleaner Setting Approximate Voltage Without High Voltage Meter A high voltage meter should be used to set the...

Page 10: ...ve it from the cabinet 6 If you are removing the power box for any length of time tape a cover over the top opening to prevent air from entering into the system Replacing A Tungsten Ionizing Wire Repl...

Page 11: ...er EAC14 11 EAC22 11 EAC20 11 12 Carbon Filters Set of 3 EAC14 12 EAC20 12 EAC20 12 13 Prefilter EAC14 13 EAC22 13 EAC20 13 14 Cell Guide Plastic EAC14 14 EAC14 14 EAC14 14 15 Collecting Cell EAC14 15...

Page 12: ...needle nose pliers gently pull contacts down or replace contacts Cells arcing excessively power light and per formance indicator light ON or flashing Cells wet from washing Allow cells to dry complete...

Page 13: ...basis for the Air Cleaner to function at its peak of efficiency The frequency of cleaning will vary from one house to another On average the cells should be cleaned every 3 months Use the chart below...

Page 14: ...NOTES 14...

Page 15: ...he defective part to General Filters Inc THERE ARE NOT EXPRESS WARRANTIES COVERING THIS ELECTRONIC AIR CLEANER OTHER THAN AS SET FORTH ABOVE THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A...

Page 16: ...of the furnace or air handler ensure that there is 115 Volt output from these terminals when the unit is run manually and is running on low speed Some manufacturers do not supply full output voltage...

Reviews: