4.9 Command Register Locations
Table 30: Command Register Locations
Register
Address
(Hex)
Parameter
Function
Data
Type
Data Range Access
0x0000
Analog Output
0-20mA current output
Numeric
Value
0-65535
(0-20.0mA)
R
0x0001
Operating Mode
View operating mode
Numeric
Value
Table 31
R
0x0002
Error Status
View present error
Bit Map
Table 32
R
0x0003 Reserved
N/A
N/A
N/A
N/A
0x0004
Model Number
View Model ID
Numeric
Value
3500 R
0x0005
Firmware Revision Firmware Revision ID
2 ASCII
chars
1
st
char is
blank, 2
nd
is:
A, B, C, …
R
0x0006 COPM
Fault
Indicates a COPM fault
on at least 1 of the
detectors
Bit Map
Bit 7 is 1 if
any COPM
fault, bits 0,
1, 2, 3
indicate
sensor id.
R
0x0007
DIP Switch
Override
Overrides the DIP
Switches at Startup to
use Flash Variables
Bit Map
0 = Options
read from
DIP, 1
means from
Flash
R/W
0x0008 Unit
Options
Indicates which options
are configured
Numeric
Value
R/W
0x0009 COM1
Address
Set/view address on
MODBUS channel 1
Numeric
Value
1-247 R/W
0x000A Reserved
N/A
N/A
N/A
N/A
0x000B
COM1
Baud Rate
Set/view baud rate on
MODBUS channel 1
Numeric
Value
Table 33
R/W
0x000C
COM1
Data Format
Set/view data format on
MODBUS channel 1
Numeric
Value
Table 23
R/W
0x000D
COPM Count
Sensor 1
Number of COPM Faults
on sensor 1
Numeric
Value
0-65535 R
0x000E
COPM Count
Sensor 2
Number of COPM Faults
on sensor 2
Numeric
Value
0-65535 R
0x000F
COPM Count
Sensor 3
Number of COPM Faults
on sensor 3
Numeric
Value
0-65535 R
0x0010
COPM Count
Sensor 4
Number of COPM Faults
on sensor 4
Numeric
Value
0-65535 R
0x0011 Reset
Relays
Remotely resets latched
alarm & warning relays
Numeric
Value
1 = reset
relays
W