CAUTION:
General Monitors requires that the FL4000 conduit entry be sealed per the
Canadian Electrical Code Handbook (Part 1, Section 18-154). Conduit seals or
approved EExd glands prevent water from entering the detector’s housing
through the conduit entry. Water entering the housing through the conduit entry
will damage the electronics and nullify the warranty.
The FL4000 is mounted as shown in Figure 16 and the overall product dimensions are depicted
in Figure 17.
NOTE
: Conduit seal must be within 18” of unit.
NOTE
: Non-hardening thread sealant should be used if the plugs are removed or re-installed
in order to preserve ingress protection rating.
Figure 16: Detector Mounting and Installation