Model MHX3C Humidistat Installation Manual

MHX3C Locations

Specifications

RANGE: 10% to 75% RH ELECTRICAL RATING: 30 VAC, 60 VA

The MHX3C can be configured for operation as a standard humidistat, high limit humidistat, or dehumidistat.  When 
using this product as a standard humidistat terminals "NO" and "C" must be used. When using this product as a high 
limit humidistat terminals "NO" and "C" and must be used. When using this product as a dehumidistat terminals "NC" 
and  "C" must be used. Use DHD3 Dial (GFI #7061) for the dehumidistat version.

WALL MOUNTING INSTRUCTIONS - Humidistat/Dehumidistat Versions

1.  Chose a location for the MHX3C about five feet above the floor on an inside wall with average room 

temperature and relative humidity conditions.  Drill a small hole in the wall and run low voltage wiring to the 
location chosen.  Pull about 6” of wire through the hole. 

2.  Gaskets:  Use the entire thin mounting gasket (both inside and outside portions) to seal the wall opening or 

use foam tape to prevent drafts from affecting the humidistat operation.  Do NOT install the thick gasket.  
(see FIG. 1)

3.  Squeeze the top and bottom of the base to release the face of the humidistat.
4.  Mount the base horizontally over the wires.  Attach directly to the wall, using the two screws provided in the 

slotted holes.

5.  Connect wires to screw terminals on the control assembly as shown in DIAGRAMS 1-5.  Replace the face.

DUCT MOUNTING ON THE RETURN AIR - WALL BASE
Humidistat/Dehumidistat versions  (optional)

Do not install the humidistat on the warm air duct or within 48” of UV light.
1.  Locate the humidistat at least 24" upstream of the humidifier or bypass on the return air duct.  Avoid areas of 

direct radiation like secondary heat exchangers in the fan compartment.  Cut a square hole in the duct 2-1/4” 
wide and 1-3/4” tall. 

2.  Gaskets:  Remove the inner portion of the mounting gasket and discard. Use the outer portion to seal between 

the plastic base and the duct. Place the thick gasket inside the wall mount base to seal off air entering through 
the vents.  Line up the base with the cut out and accurately mark the holes thru the plastic duct mount plate. 
(see FIG. 1)

3.  Remove the humidistat and drill four 3/32” mounting holes. 
4.  Place the outer portion of the mounting gasket on the plastic base and mount the base with four screws.  Low 

voltage wire may enter the humidistat under the gasket.

5.  Connect wires to screw terminals on the control assembly as shown in DIAGRAMS 1-5.  Replace the face. 

Wall or Duct Mount

 

Thin Gasket

Face

FIG. 1

WALL

 MOUNT: Use  

Outer & Inner Portions

DUCT

 MOUNT:  Use  

ONLY Outer Portion

Mounting 

Base 

Thick Gasket 

DUCT

 MOUNT ONLY

Summary of Contents for MHX3C

Page 1: ...URN OFF POWER TO THE HVAC SYSTEM prior to installing or servicing the humidifier or humidistat Improper operation can result in over or under humidification Improper voltage can cause malfunction or damage to the control All local building and electrical codes must be followed The technical specifications for this product and the contents of the user manual are subject to change without notice WAR...

Page 2: ...Attach directly to the wall using the two screws provided in the slotted holes 5 Connect wires to screw terminals on the control assembly as shown in DIAGRAMS 1 5 Replace the face DUCT MOUNTING ON THE RETURN AIR WALL BASE Humidistat Dehumidistat versions optional Do not install the humidistat on the warm air duct or within 48 of UV light 1 Locate the humidistat at least 24 upstream of the humidifi...

Page 3: ...distat L1 N G Humidifier Control Leads Yellow Wires Humidifier Power Cord Humidifier 24V Aux Power Red Wires 120V Switched With Furnace Heating Cycle DIAGRAM 5 Wiring 120V 1137 1000 Power Humidifiers With Constant 120V Supply Humidifier Control Leads Yellow Wires Humidifier Power Cord Humidifier 24V Aux Power Red Wires L1 N G 727 58 24V Transformer Omit if Power Supply is 20 30 VAC 120V Switched W...

Page 4: ...and C are used on the humidistat These are the contacts for humidification 3 Check voltage at terminals NO and C There should be no voltage for an Elite Steam or 1137 1000 power humidifier Voltage should be 20 30 VAC from most others 4 Verify humidifier operation by bypassing the humidistat Ideal humidity is not achieved 1 Excess air infiltration Seal sources of air loss 2 Technical fault with hum...

Reviews: