Operation
2.2 HOUrMETEr - wITH rESET
The Hourmeter tracks hours of operation for scheduled maintenance
(see chart) (Figure 6).
Operation:
Push and release the reset button to toggle between
screens. The hours count backwards from the set interval as
shown in the chart.
When the meter reaches 5 hours,the text "CHG OIL" (or "SVC AIR
FILTER" or "CHG PLUG") will flash continually for two minutes.
After this time, the meter will go back to displaying the total hours
of the unit (for 2 minutes). This cycle will repeat for the entire 5
hours.
When the service interval reaches zero hours, the text "NOW"
replaces the hours remaining.
For a new generator for instance, the message will say "CHG OIL"
then flash "in 30". This means that in 30 hours, the oil will need to
be changed. Pressing the button a few more times will bring the
meter back to the screen that shows the total hours run.
reset:
Toggle to the alert that you wish to reset then hold the
button down for 9 seconds. The maintenance hours are reset when
the display shows "0000.0".
NOTE:
The hour glass graphic will flash on and off when the engine
is running. This signifies that the meter is tracking hours of
operation.
Figure 6 – Hourmeter
HOUR GLASS
GRAPHIC
RESET BUTTON
(IF EQUIPPED)
0000.0
2.3 cONNEcTION PLUGS
2.3.1 230 Vac, 15 aMP, as/NZs 3112 recePTacLe
This is a 230 Volt outlet protected against overload by a 15 Amp
push-to-reset circuit breaker (Figure 7). Use each socket to power
230 Volt AC, single phase, 50 Hz electrical loads requiring up to a
combined 3450 watts (3.4 kW) or 15 Amps of current. Use only
high quality, well-insulated, 3-wire grounded cord sets rated for
230 Volts at 15 Amps (or greater).
Keep extension cords as short as possible, preferably less than 5
meters long, to prevent voltage drop and possible overheating of
wires.
Figure 7 – 230 Volt ac, 15 amp, as/NZs 3112
receptacle
Hourmeter (with reset) chart
Message
Frequency of Message
Interval
Duration of message
CHG OIL
Initial break-in period
First 30 Hours
ON/OFF for 2 minutes in a 5
hour period
CHG OIL
Re-occuring
100 hours
SVC AIR FILTER
Re-occuring
200 hours
CHG PLUG
Re-occuring
200 hours