Generac Power Systems PWRell 0009890 Owner'S Manual Download Page 15

Owner’s Manual for Generac PWRcell Battery

11

General Information

Blackstart

NOTE: 

Blackstart  voltage  must  be  13V  or  greater  to 

power the system.

NOTE: 

The Generac PWRcell Battery must be enabled 

to blackstart. If the Generac PWRcell Battery is disabled, 
perform a manual enable. See 

Manual Enable

.

Blackstart allows the Generac PWRcell Battery to power 
up a Generac PWRcell system that is powered down and 
has no other sources of power available.
See 

Figure 2-7

.

  To  Blackstart,  turn  Battery  Disconnect 

(A)  ON.  LED  (B)  will  light  green  if  Generac  PWRcell  is 
enabled and the battery has sufficient charge. 

ON

OFF

BATTERY DISCONNECT

A

B

0009896

Figure 2-7. Blackstart

After initialization is complete, the Generac PWRcell Bat-
tery automatically energizes REbus and begins support-
ing  REbus  and  protected  AC  loads  connected  to  the
Generac  PWRcell  Inverter,  and  charging  from  the  Gen-
erac PWRcell PV Link and other sources.

Manual Enable

See 

Figure 2-7

If LED (B) lights solid red when Battery 

Disconnect  switch  is  turned  ON,  the  Generac  PWRcell 
Battery is disabled. 
Generac PWRcell can be disabled if:

Disabled by a user.

A safety shutdown was performed.

Generac PWRcell reached a critically low state of 
charge and no REbus voltage was present

No grid power was available during commissioning.

NOTE: 

To  avoid  the  need  for  a  manual  enable,  keep 

Generac  PWRcell  enabled,  connected  to  REbus,  and 
with Battery Disconnect ON.

To perform a Manual Enable:

1.

Turn Battery Disconnect (A) ON.

2.

If  the  unit  is  disabled,  LED  (B)  will  light  red  for  3 
seconds.

3.

While the LED is still red, turn Battery Disconnect 
OFF.

4.

Perform steps 1-3 three times in total.

5.

Turn Battery Disconnect ON for a fourth time. 

Generac  PWRcell  is  now  enabled.  If  the  battery  has 
sufficient charge, LED (B) will light green to indicate the 
battery  is  enabled  and  the  system  will  Blackstart  and 
resume normal operation

Summary of Contents for PWRell 0009890

Page 1: ...Loss of life This product is not intended to be used in a critical life support application Failure to adhere to this warning could result in death or serious injury Register your Generac product at...

Page 2: ...ion is performed promptly and to have the equipment checked periodically by an ASD Normal maintenance service and replacement of parts are the responsibility of the owner operator and as such are not...

Page 3: ...rial Number Locations 6 Unit Dimensions 6 Component Locations 7 Battery Disconnect Switch 7 Battery Status LED 7 About Generac PWRcell Battery 8 Communication 8 System Operational Modes 8 Inverter Con...

Page 4: ...iv Owner s Manual for Generac PWRcell Battery This page intentionally left blank...

Page 5: ...m on how to correctly start operate and stop the unit in case of emergency Safety Rules The manufacturer cannot anticipate every possible cir cumstance that might involve a hazard The alerts in this m...

Page 6: ...d result in death serious injury and equipment or property damage IMPORTANT NOTE See individual unit specifications for required maintenance and run times pertaining to use Connecting Generac PWRcell...

Page 7: ...ould result in death or serious injury 000155a WARNING Electric shock Only a trained and licensed electrician should perform wiring and connections to unit Failure to follow proper installation requir...

Page 8: ...Shutdown press and hold Shutdown A Safety shutdown LED B will illuminate and LCD screen C will indicate Safety Shutdown has been initiated REbus Inverter Internet Shutdown hold 009656 A C B Figure 1 1...

Page 9: ...Ebus Communication Protocol REbus DC Nanogrid Voltage Input Output VDC 360 420 Round Trip Efficiency DC to DC 96 5 Temperature Operating Temperature Limits F C 41 113 5 45 Recommended Temperature Rang...

Page 10: ...ameplate Record the information from these tags so it is available if the tags are lost or damaged When ordering parts or requesting assistance you may be asked to provide this information A 0009891 F...

Page 11: ...battery monitoring system BMS electronics NOTE Battery Disconnect can be locked in the OFF position if required NOTE Turn Battery Disconnect OFF whenever system will be powered down and left inactive...

Page 12: ...enerac PV Link Optimizers F Grid C Generac PWRcell Battery G Loads D REbus H Protected Loads Communication All communication between REbus devices takes place over the REbus conductors using Power Lin...

Page 13: ...able for Self Supply and other non backup uses but lowers the islanding reserve in the event of an outage Raising this setpoint lowers capacity available for Self Supply and related modes but increase...

Page 14: ...rty damage While in Sleep Mode Generac PWRcell performs Power Searches at regular intervals During a Power Search Generac PWRcell wakes up energizes the REbus Nanogrid and scans for potential sources...

Page 15: ...PWRcell Inverter and charging from the Gen erac PWRcell PV Link and other sources Manual Enable See Figure 2 7 If LED B lights solid red when Battery Disconnect switch is turned ON the Generac PWRcel...

Page 16: ...12 Owner s Manual for Genera PWRcell Battery General Information This page intentionally left blank...

Page 17: ...ed air or water NOTE Allow filter to dry before reinstalling 5 Reinstall filter If air filter is damaged contact Generac Customer Service at 1 888 GENERAC 1 888 436 3722 or visit www gen erac com for...

Page 18: ...Dealer shall prepare a written decommissioning plan that provides the overview of the decommissioning process developed specifically for the Generac PWRCell Battery system that is to be decommissioned...

Page 19: ......

Page 20: ...ghts reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S45 W29290...

Reviews: