Commissioning and Setup
Installation Manual for Generac PWRCell Inverter
25
Section 6: Commissioning and Setup
System Configuration
The PWRcell system is a flexible, highly customizable
system that can be configured in a number of ways to
meet customer need. Correct system configuration
requires selecting the right equipment and the correct
system mode for the system. See the Generac PWRcell
Inverter Owner’s Manual for information on system
modes and other user-configurable settings.
General Information
All REbus devices are configured and controlled through
the Generac PWRcell Inverter. Connected devices will
appear on the LCD display.
NOTE:
See
Commissioning Multiple Inverter Sys
for instructions on commissioning multiple inverter
systems.
Commissioning the System
NOTE:
See the Generac PWRcell Commissioning Quick
Start Guide for more information.
Before powering up the system for the first time:
•
Verify AC voltage is within the specified range for
system configuration.
– 240 V split-phase (108-130 VAC Line to Neutral)
– 208 V 3-phase (108-130 VAC Line to Neutral)
•
Verify all wiring terminations are tight and secure.
•
Verify DC wiring field terminations are secure and
polarity is correct.
•
Verify DC disconnects for all connected devices
are turned ON.
Commissioning consists of seven steps:
1.
Register system.
2.
Energize the PWRcell inverter with AC power.
3.
Select Inverter system mode.
4.
Configure inverter settings.
5.
Select inverter compliance setting (optional).
6.
Select ESS Grid Usage Mode (optional).
7.
Enable REbus devices.
8.
Test islanding.
Registration
NOTE:
If the system will not be connected to the Inter
-
net, installer will not be able to take advantage of PWR
-
fleet, the home owner will not have access to the
PWRview app, and warranty will be limited to five years.
Contact Generac at 1-888-ACTIVATE to complete the
registration.
NOTE:
Registering an inverter automatically registers all
REbus system components connected to that inverter.
Every REbus-enabled device can be monitored from the
PWRfleet fleet management platform and the
PWRview™ online monitoring system and mobile app.
To register a system for PWRview monitoring:
1.
See
. Locate the serial number and reg
-
istration code on the registration decal on the front
of the inverter. This information will be required for
registration.
2.
Navigate to
using a mobile device scan the registration label
QR code.
3.
Follow the on-screen prompts to complete the
profile.
.
Figure 6-1. Registration Decal
REGISTER YOUR SYSTEM
Go to
https://pwrfleet.generac.com/
to register
or scan the code above.
SERIAL NUMBER:
REGISTRATION CODE:
PEEL AWAY
XXXXX-XXXXX
RRRR-RRRR