COMMERCIAL 130 kW 

KW RATING 

130

ENGINE SIZE 

6.8 Liter V-10

GENERATOR OUTPUT VOLTAGE/KW - 60Hz 

KW 

AMP 

CB Size

  120/240V, single phase, 1.0 pf 

130 

541.6 

600

  120/208V, 3-phase, 0.8 pf 

130 

451.5 

500

  120/240V, 3-phase, 0.8 pf 

130 

391.3 

450

  277/480V, 3-phase, 0.8 pf 

130 

195.6 

225

GENERATOR LOCKED ROTOR KVA
 AVAILABLE @ VOLTAGE DIP OF 35%
  Single phase or 208V & 240V 3-phase 

 

270

 480V 

3-phase 

 

320

   

 

 

ENGINE FUEL CONSUMPTION 

(Natural Gas) (Propane)

 

 

Natural Gas 

Propane  

  

 

 

(ft3/hr.) (gal/hr.) 

cu 

ft/hr

 Exercise 

cycle 

 

135 

1.48 

54.5 

  25% of rated load 

 

482 

5.28 

194.3

  50% of rated load 

 

927 

10.15 

373.5

  75% of rated load 

 

1292 

14.15 

520.7

  100% of rated load 

 

1786 

19.56 

719.8

   
ENGINE COOLING
 Air 

flow 

(inlet air including alternator and combustion air)

 ft3/hr. 6,450

  System coolant capacity 

US gal. 

4.5

  Heat rejection to coolant 

 BTU/hr. 

496,000

  Max. operating air temp. on radiator 

°C (°F) 

60 (150)

  Max. ambient temperature 

°C (°F) 

50 (140)

COMBUSTION AIR REQUIREMENTS
  Flow at rated power 60 Hz 

cfm 

336

   
SOUND EMISSIONS IN DBA
  db(A) @ 23 feet in exercise mode 

 

65 

  db(A) @ 23 feet at normal operating load 

 

75 

 
EXHAUST
  Exhaust flow at rated output 60 Hz 

cfm 1,119 

  Exhaust temp. at muffler outlet 

°F 

970 

ENGINE PARAMETERS
  Rated synchronous RPM 

60 Hz 

3000

  HP at rated KW 

60 Hz 

210

POWER ADJUSTMENT FOR AMBIENT CONDITIONS
 Temperature 

Deration

   

3% for every 10 °C above - °C 

25 

   

1.65% for every 10 °F above - °F 

77

 Altitude 

Deration 

   

1% for every 100 m above - m 

183 

 

   

3% for every 1000 ft. above - ft. 

600

OPERATING DATA

COMMERCIAL 130 kW

RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility 
source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and 
specifications are subject to change without notice. Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power 
and condition, etc.