![Generac Power Systems 005845-0 Owner'S Manual Download Page 9](http://html1.mh-extra.com/html/generac-power-systems/005845-0/005845-0_owners-manual_2209394009.webp)
7
2.4 HOW TO USE THE GENERATOR
If there are any problems operating the generator, please call the
generator helpline at 1-888-436-3722.
The engine exhaust fumes contain carbon monoxide, which
•
can you cannot see or smell. This poisonous gas, if breathed
in sufficient concentrations, can cause unconsciousness or
even death.
Adequate, unobstructed flow of cooling and ventilating air
•
is critical to correct generator operation. Do not alter the
installation or permit even partial blockage of ventilation
provisions, as this can seriously affect safe operation of the
generator. The generator MUST be operated outdoors.
This exhaust system must be properly maintained. Do nothing
•
that might render the exhaust system unsafe or in noncompliance
with any local codes and/or standards.
The manufacturer recommends installing a battery operated
•
carbon monoxide alarm indoors, according to the manufacturers
instructions.
2.4.1 SYSTEM GROUND
The generator has a system ground that connects the generator
frame components to the ground terminals on the AC output
receptacles. The system ground is bonded to the AC neutral wire
in the generator control panel via a jumper wire.
2.4.1.1 Special Requirements
There may be Federal or State Occupational Safety and Health
Administration (OSHA) regulations, local codes, or ordinances that
apply to the intended use of the generator.
Please consult a qualified electrician, electrical inspector, or the
local agency having jurisdiction:
In some areas, generators are required to be registered with
•
local utility companies.
If the generator is used at a construction site, there may be
•
additional regulations which must be observed.
2.4.1.2 Connecting to a Building’s Electrical System
Connections for standby power to a building’s electrical system
must be made by a qualified electrician. The connection must
isolate the generator power from utility power or other alternative
power sources and must comply with all applicable laws and
electrical codes.
2.4.2 GROUNDING THE GENERATOR
The National Electrical Code requires that the frame
and external electrically conductive parts of this
generator be properly connected to an approved earth
ground.
Local electrical codes may also require proper grounding of
the unit (Figure 6). For that purpose, connecting a No. 10 AWG
(American Wire Gauge) stranded copper wire to the grounding lug
and to an earth-driven copper or brass grounding rod (electrode)
provides adequate protection against electrical shock. However,
local codes may vary widely.
Consult with a local electrician for
grounding requirements in the area.
Proper grounding of the generator will help prevent electrical
shock
in the event of a ground fault condition in the generator or in
connected electrical devices. Proper grounding also helps dissipate
static electricity, which often builds up in ungrounded devices.
Figure 6 – Generator Ground Location
XG6500 & XG7000
GROUND LOCATION
XG8000
GROUND
LOCATION
Section 2 – Operation
Portable Generator System
Summary of Contents for 005845-0
Page 19: ...17 Section 6 Notes...
Page 41: ...39 NOTAS Secci n 6 Notas...
Page 63: ...61 REMARQUES Section 6 Remarques...
Page 64: ...62 Section 6 Remarques REMARQUES...