Modbus Map
Integrated Load Center Owner’s Manual
27
Section 6: Modbus Map
Description
This document describes the transfer switch data
available via the secondary communication port on the
touch screen.
Communication Settings
Modbus Settings
RS232 Pinout
Data Map
Protocol
RS-232
Baud rate
9600
Data bits
8
Parity
None
Stop bits
1
Station
157
Register
Data
Notes
500
[0:15]
Bit 6: Automatic Mode
Bitmap
501
[0:15]
Bit 0: Util ok
Bit 1: Util loss delay
Bit 2: Gen starting
Bit 3: Gen ok
Bit 4: Synching
Bit 5: TDN
Bit 6: On generator
Bit 7: Util recover delay
Bit 8: Gen minimum run
Bit 9: Gen cooldown
Bit 10: Gen stop
Bit 11: Exercising
Bit 12: System fault
Bit 13: Transfer to gen
Bit 14: Transfer to util
Bit 15: Warmup
Bitmap
502
[0:15]
Bit 1: In test mode
Bit 2: In fast test mode
Bitmap
503
Measured Va
AB line-to-line (AN for single phase)
504
Measured Vb
BC line-to-line (BN for single phase)
505
Measured Vc
CA line-to-line (unused for single phase)
506
Measured Ia
507
Measured Ib
508
Measured Ic
Unused for single phase
509
Utility Volts
Average
510
Utility Current
Average
511
Utility Frequency
Average, x100
512
Utility Power Factor
x100
513
Utility kW
Average
514
Generator Volts
Average
515
Generator Frequency
Average
Summary of Contents for 004877
Page 10: ...General Information 6 Integrated Load Center Owner s Manual This page intentionally left blank...
Page 14: ...Installation 10 Integrated Load Center Owner s Manual This page intentionally left blank...
Page 30: ...Maintenance 26 Integrated Load Center Owner s Manual This page intentionally left blank...
Page 32: ...Modbus Map 28 Integrated Load Center Owner s Manual This page intentionally left blank...
Page 38: ...Drawings and Diagrams 34 Integrated Load Center Owner s Manual Wiring Diagram 0L4634 C 1 of 2...
Page 39: ...Drawings and Diagrams Integrated Load Center Owner s Manual 35 Wiring Diagram 0L4634 C 2 of 2...
Page 43: ......