Operation
14
Integrated Load Center Owner’s Manual
Main Contacts at Normal (Utility)
See
. Load terminals are connected to the
normal (utility) terminals. Window “A” will display the
word “ON”; Window “B” the word “OFF”.
Figure 4-2. Main Contacts at Normal (Utility)
Main Contacts at Neutral
See
. Load terminals are disconnected from
both power supply terminals. The word “OFF” will be
displayed in both Windows “A” and “B.”. This occurs
when the solenoid coil is kept energized.
This position cannot occur utilizing the manual handle
operator. It is only during electrical operation that both
contacts are momentarily held open via the control's
neutral time delay (TDN) feature.
Figure 4-3. Main Contacts at Neutral
Main Contacts at Standby
(Emergency)
See
. Load terminals are connected to the
standby (emergency) power supply. Window “B” will
display the word “ON”; Window “A” the word “OFF”
(
Figure 4-4. Main Contacts at Standby (Emergency)
Utility source selected: “A” position ON, “B” position OFF
A
Load
B
Emergency “B” position
C
Utility “A” position
Neutral (tripped) position: “A” and “B” positions both OFF
A
Load
B
Emergency “B” position
C
Utility “A” position
001250a
B
A
C
001251a
B
A
C
Emergency source selected:
“A” position OFF, “B” position ON
A
Load
B
Emergency “B” position
C
Utility “A” position
001252a
B
A
C
Summary of Contents for 004877
Page 10: ...General Information 6 Integrated Load Center Owner s Manual This page intentionally left blank...
Page 14: ...Installation 10 Integrated Load Center Owner s Manual This page intentionally left blank...
Page 30: ...Maintenance 26 Integrated Load Center Owner s Manual This page intentionally left blank...
Page 32: ...Modbus Map 28 Integrated Load Center Owner s Manual This page intentionally left blank...
Page 38: ...Drawings and Diagrams 34 Integrated Load Center Owner s Manual Wiring Diagram 0L4634 C 1 of 2...
Page 39: ...Drawings and Diagrams Integrated Load Center Owner s Manual 35 Wiring Diagram 0L4634 C 2 of 2...
Page 43: ......