Generac Portable Products XG6500 Owner'S Manual Download Page 8

6

2.1.1  BATTERY CONNECTION (XG7000E & XG8000E)

NOTE:

The battery shipped with the generator has been fully charged. 

A battery may lose some of its charge when not in use for 

prolonged periods of time. If the battery is unable to crank 

the engine, plug in the 12V charger included in the accessory 

box (see the Charging the Battery section). RUNNING THE 

GENERATOR DOES NOT CHARGE THE BATTERY.

The positive battery wire was deliberately left detached for 

shipping. To operate the unit, attach this wire to the terminal on 

the starter motor as shown. Do not overtighten. Slide the attached 
rubber boot over the starter terminal. See Figure 4.

Figure 4 – Battery Connection

ENGINE

STARTER

POSITIVE (+)

BATTERY CABLE

2.2 HOURMETER

The Hourmeter tracks hours of operation for scheduled 

maintenance:
There will be a one time break in "CHG OIL" message that flashes 

with the elapsed time in hours and tenths after the first 30 hours 

of operation.
This message will actually begin flashing at 29 hours and disable 

itself at 31 hours providing a two hour window to perform the 

service.
There will be a subsequent "CHG OIL" message every 100 hours. 

The message will flash one hour before and one hour after each 

100 hour interval, again providing a two hour window to perform 

service.
Every 200 hours the "SVC" icon on the lower left hand corner of 

the display will flash. The message will flash one hour before and 

one hour after each 200 hour interval providing a two hour window 

to perform service.

When the hour meter is in the Flash Alert mode, the maintenance 

message will always alternate with elapsed time in hours and 

tenths. The hours will flash four times, then alternate with the 

maintenance message four times until the meter resets itself.

100 hours - CHG OIL — Oil Change Interval (Every 100 hrs)

• 

200 hours - SVC — Air Filter Interval (Every 200 hrs)

• 

2.3  CORD SETS AND CONNECTION PLUGS

2.3.1  120 VAC, 20 AMP, GFCI DUPLEX RECEPTACLE

This is a 120 Volt outlet protected against overload by a 20 Amp 

push-to-reset circuit breaker (Figure 5). Use each socket to power 

120 Volt AC, single phase, 60 Hz electrical loads requiring up to a 

combined 2400 watts (2.4 kW) or 20 Amps of current. Use only 

high quality, well-insulated, 3-wire grounded cord sets rated for 

125 Volts at 20 Amps (or greater).
Keep extension cords as short as possible, preferably less than 

15 feet long, to prevent voltage drop and possible overheating of 
wires.

2.3.2  120/240 VAC, 30 AMP RECEPTACLE

Use a NEMA L14-30 plug with this receptacle (rotate to lock/

unlock). Connect a suitable 4-wire grounded cord set to the plug 

and to the desired load. The cord set should be rated for 250 Volts 

AC at 30 Amps (or greater) (Figure 5).
Use this receptacle to operate 120 Volt AC, 60 Hz, single phase 

loads requiring up to 3600 watts (3.6 kW) of power at 30 Amps 

or 240 Volt AC, 60 Hz, single phase loads requiring 6,500 to 8000 

watts of power, depending on the model. The outlet is protected by 

a 30 Amp circuit breaker.

Figure 5 – Generator Receptacles

120 VAC 20A 

GFCI RECEPTACLE

120/240 VAC 30A 

 RECEPTACLE

Operation

Summary of Contents for XG6500

Page 1: ...www generac com or 1 888 436 3722 Owner s Manual XG Series 6 500 8 000 Watt Portable Generator MODELS 005796 0 XG6500 005797 0 XG7000 005798 0 XG7000E 005800 0 XG8000 005747 0 XG8000E...

Page 2: ...Adding Gasoline 9 2 8 To Start the Engine 10 2 8 1 Manual Recoil Starting 10 2 8 2 Electric Starting XG7000E XG8000E 11 2 9 Stopping the Engine 11 2 10 Low Oil Pressure Shutdown System 11 2 10 1 Resta...

Page 3: ...US SITUATION OR ACTION WHICH IF NOT AVOIDED WILL RESULT IN DEATH OR SERIOUS INJURY Indicates a hazardous situation or action which if not avoided could result in death or serious injury Indicates a ha...

Page 4: ...ds and barriers are in place before operating the generator Never handle any kind of electrical cord or device while standing in water while barefoot or while hands or feet are wet DANGEROUS ELECTRICA...

Page 5: ...NATIONAL BUILDING CODE available from the American Insurance Association 85 John Street New York N Y 10038 3 AGRICULTURAL WIRING HANDBOOK available from the Food and Energy Council 909 University Ave...

Page 6: ...ne at 1 888 775 6937 1 2 1 ASSEMBLING THE WHEEL KIT AND FRAME FOOT The wheel kit is designed to greatly improve the portability of the generator You will need the following tools to install the wheel...

Page 7: ...o reset circuit breaker to protect the generator against electrical overload 8 Circuit Breakers AC The 30 Amp receptacle is protected with a pair of push to reset circuit breakers to protect the gener...

Page 8: ...interval providing a two hour window to perform service When the hour meter is in the Flash Alert mode the maintenance message will always alternate with elapsed time in hours and tenths The hours wil...

Page 9: ...y and Health Administration OSHA regulations local codes or ordinances that apply to the intended use of the generator Please consult a qualified electrician electrical inspector or the local agency h...

Page 10: ...ading the unit Add up the total wattage of all electrical devices to be connected at one time This total should NOT be greater than the generator s wattage capacity The rated wattage of lights can be...

Page 11: ...minimum American Petroleum Institute API Service Class SJ SL or better Use no special additives Select the oil s viscosity grade according to the expected operating temperature also see chart Above 40...

Page 12: ...r use engine or carburetor cleaner products in the fuel tank as permanent damage may occur 2 8 TO START THE ENGINE Never start or stop engine with electrical devices plugged into the receptacles AND d...

Page 13: ...Y XG7000E XG8000E n Do not permit smoking open flame sparks or any other source of heat around a battery Wear protective goggles rubber apron and rubber gloves when working around a battery Battery el...

Page 14: ...the following Fuel System Air Induction System Fuel Tank Intake pipe manifold Fuel Cap Air cleaner Carburetor Ignition System Fuel Lines Spark plug Evaporative Control System Ignition module Carbon C...

Page 15: ...hose and oil fill plug to drain oil completely into a suitable container When oil has completely drained install oil drain cap and tighten securely Place a suitable container beneath the oil filter an...

Page 16: ...it for storage NEVER store engine with fuel in tank indoors or in enclosed poorly ventilated areas where fumes may reach an open flame spark or pilot light as on a furnace water heater clothes dryer o...

Page 17: ...charger included in the accessory box see the Charging a Battery section RUNNING THE GENERATOR DOES NOT CHARGE THE BATTERY The battery shipped with the generator has been provided fully charged To rep...

Page 18: ...tuck open or closed 12 Engine has lost compression 1 Turn Fuel shut off ON 2 Clean or replace air cleaner 3 Fill fuel tank 4 Drain fuel tank and fill with fresh fuel 5 Connect wire to spark plug 6 Rep...

Page 19: ...17 Notes...

Page 20: ...market parts not made supplied or approved by Generac You are responsible for contacting a Generac Authorized Warranty Dealer as soon as a problem occurs The warranty repairs should be completed in a...

Page 21: ...t repaired or replaced under the ECS warranty shall be warranted for the remainder of the period prior to the first scheduled replacement point for that part 4 Repair or replacement of any warranted e...

Page 22: ...nostics performed by individuals other than Guardian Generac authorized dealers not authorized in writing by Generac Power Systems Failures due but not limited to normal wear and tear accident misuse...

Page 23: ...c com or 1 888 436 3722 Manual del propietario XG Series Generador port til de 6 500 8 000 vatios MODELO 005796 0 XG6500 005797 0 XG7000 005798 0 XG7000E 005800 0 XG8000 005747 0 XG8000E 2A OS GARANT...

Page 24: ...11 Mantenimiento 11 3 1 Cronograma de mantenimiento 11 3 2 Especificaciones del producto 11 3 2 1 Especificaciones del generador 11 3 2 2 Especificaciones del motor 12 3 2 3 Informaci n sobre emision...

Page 25: ...ca una situaci n peligrosa o acci n que si no se evita podr a traer como resultado la muerte o un da o serio CUIDADO Indica una situaci n peligrosa o acci n que si no se evita puede traer como resulta...

Page 26: ...nerador Aseg rese que todas las cubiertas protecciones y barreras apropiadas se encuentren en su lugar antes de operar el generador No manipule ningun tipo de dispositivo el ctrico mientras est de pie...

Page 27: ...res c digos regulaciones o leyes pertinentes la informaci n publicada listada abajo puede usarse como gu a para la operaci n de este equipo Siempre consulte la revisi n m s reciente aplicable para el...

Page 28: ...888 775 6937 1 2 1 ENSAMBLAJE DE LA RUEDA El kit de la rueda est dise ado para mejorar en gran medida la portabilidad del generador Usted necesitar las siguientes herramientas para instalar el kit de...

Page 29: ...provisto con un interruptor de circuito de presionar para reiniciar con el fin de proteger al generador contra sobrecargas el ctricas 8 Interruptores de circuito AC El recept culo de 30 amps est prote...

Page 30: ...as est en el modo de alerta de destello Flash Alert el mensaje de mantenimiento siempre alternara con el tiempo transcurrido en horas y d cimos Las horas destellar n cuatro veces luego alternar con lo...

Page 31: ...o de CA en el panel de control del generador a trav s de un cable jumper Requerimientos especiales Puede haber regulaciones federales o estatales respecto a la salud y seguridad ocupacional OSHA c dig...

Page 32: ...del generador La potencia nominal de las luces puede leerse en las mismas bombillas La potencia nominal de las herramientas aparatos y motores normalmente se puede encontrar en la etiqueta de datos o...

Page 33: ...de la toma de aceite y retire la tapa Llene lentamente el motor con aceite a trav s de la abertura hasta que llege a su marca de lleno Deje de llenar ocasionalmente para revisar el nivel de aceite El...

Page 34: ...siga la misma secuencia de choke listada arriba NOTA Si el motor dispara pero no sigue funcionando tire la palanca de choke a Full Choke y repita las instrucciones de arranque IMPORTANTE No sobrecarg...

Page 35: ...panel de control cuando el generador vaya a usarse NOTA No use el cargador dem bater as por m s de 48 horas en una carga 3 1 CRONOGRAMA DE MANTENIMIENTO Siga los intervalos del calendario Se requiere...

Page 36: ...o negligencia del operador Para recibir el valor total de la garant a el operador debe hacer el mantenimiento del generador tal como se instruye en este manual Se necesitar hacer algunos ajustes perio...

Page 37: ...ado 3 3 6 REEMPLAZO DE LA BUJ A Use buj as Champion RC14YC o equivalentes Reemplace la buj a una vez al a o Esto ayudar a que el motor arranque con mayor facilidad y funcione mejor 1 Detenga el motor...

Page 38: ...de cidos durante el almacenamiento Los gases cidos pueden da ar el sistema de combustible de un motor durante el almacenamiento Para evitar problemas con el motor el sistema de combustible deber vacia...

Page 39: ...apropiados en exteriores lejos de las flamas abiertas Aseg rese de que el motor est fr o No fume en la cercan a ni encienda cigarro alguno Presione la v lvula de combustible del panel de control y ret...

Page 40: ...de combustible a ON 2 Limpie o reemplace el limpiador de aire 3 Llene el tanque de combustible 4 Drene y llene el tanque de combustible con gasolina fresca 5 Conecte el cable a la buj a 6 Reemplace l...

Page 41: ...17 Notas...

Page 42: ...epuestos falsos o del mercado negro no fabricados suministrados o aprobados por Generac Usted es responsable de contactar a un concesionario autorizado de garant a de Generac tan pronto se presente el...

Page 43: ...mer punto de reemplazo programado para aquella parte 4 La reparaci n o reemplazo de cualquier parte garantizada relacionada a las emisiones bajo esta garant a ECS deber realizarse sin costo alguno par...

Page 44: ...ferentes a los concesionarios autorizados por Guardian Generac que no est n autorizados por escrito por Generac Power Systems Fallas debido a pero no limit ndose a el uso y desgaste normal accidente m...

Reviews: