Generac Portable Products XG6500 Owner'S Manual Download Page 13

2.8.1  ELECTRIC STARTING (XG7000E & XG8000E)

To start the engine, press and hold the Start/Run/Stop switch in 

• 

the “Start” position. The engine will crank and attempt to start. 

When the engine starts, release the switch to the run position.

When the engine starts, push choke knob to “1/2 Choke” 

• 

position until the engine runs smoothly and then fully in to the 

“Run” position. If engine falters, pull choke knob back out to 

“1/2 Choke” position until the engine runs smoothly and then 

to “Run” position.

This generator is also equipped with a manual recoil starter 

• 

which may be used if the battery is discharged.

NOTE:

The engine Start/Run/Stop switch must be in the RUN 

position when using the manual recoil starter. 

2.9  STOPPING THE ENGINE

Shut off all loads, then unplug the electrical loads from generator 

• 

panel receptacles. Never start or stop the engine with electrical 

devices plugged in and turned on.

Let engine run at no-load for several minutes to stabilize the 

• 

internal temperatures of engine and generator.

Move Start/Run/Stop or On/Off switch to the “Off” position.

• 

Close fuel valve.

• 

2.10 LOW OIL PRESSURE SHUTDOWN SYSTEM

The engine is equipped with a low oil pressure sensor that shuts 

down the engine automatically when the oil pressure drops below 

5 psi. A delay built into the low oil shutdown system allows oil 

pressure to build during starting. The delay allows the engine to 

run for about 10 seconds before sensing oil pressure. If the engine 

shuts down by itself and the fuel tank has enough gasoline, check 

engine oil level.

2.10.1 RESTARTING

If trying to restart the engine within 10 seconds after it shuts down, 

the engine may NOT start. The system needs 5 to 10 seconds to 

reset.
If the engine is restarted after such a shutdown and the low oil 

pressure has not been corrected, the engine will run for about 10 

seconds as described above and then stop.

2.11 CHARGING THE BATTERY 

(XG7000E & XG8000E)

n

 

Do not permit smoking, open flame, sparks 

or any other source of heat around a battery. 

Wear protective goggles, rubber apron and 

rubber gloves when working around a battery. 

Battery electrolyte fluid is an extremely 

corrosive sulfuric acid solution that can cause 

severe burns. If spill occurs flush area with 

clear water immediately. 

 Storage batteries give off explosive hydrogen 

gas while recharging. An explosive mixture will 

remain around the battery for a long time after 

it has been charged. The slightest spark can 

ignite the hydrogen and cause an explosion. 

Such an explosion can shatter the battery and 

cause blindness or other serious injury.

Use battery charger plug to keep the battery charged and ready 

for use. Battery charging should be done in a dry location.

1.  Plug charger into “Battery Charger Input” jack, located on the 

control panel. Plug wall receptacle end of the battery charger 

into a 120 Volt AC wall outlet.

2.  Unplug battery charger from wall outlet and control panel jack 

when generator is going to be in use.

NOTE:

Do not use the battery charger for more than 48 hours at one 

charge.

3.1 MAINTENANCE SCHEDULE

Follow the calendar intervals. More frequent service is required 

when operating in adverse conditions noted below.
Check Oil Level 

At Each Use

Change Oil and Oil Filter‡ 

*Every Season/Every 100 Hours

Clean Spark Arrestor Screen 

*Every Season/Every 100 Hours

Service Air Cleaner 

**Every Season/Every 200 Hours

Replace Spark Plug 

Every Season

‡ 

Change oil after first 30 hours of operation then every season.

*   Change oil and oil filter every month when operating under heavy load or in 

high temperatures.

**   Clean more often under dirty or dusty operating conditions. Replace air 

cleaner parts if very dirty.

3.2 PRODUCT SPECIFICATIONS

3.2.1 GENERATOR SPECIFICATIONS

Model # ............................................................... 005800-0, 005747-0

Rated Max. Power ...................................................................8.0 kW**
Surge Power ................................................................................10 kW
Rated AC Voltage ......................................................................120/240
Rated Max AC Load
  Current @ 240V .............................................................33.3 Amps**
  Current @ 120V .............................................................66.7 Amps**
Rated Frequency .................................................... 60 Hz @ 3600 RPM
Phase ................................................................................ Single Phase
Rated DC Voltage ...................................................................... 12 Volts
Battery Type .................................................................... 10 AH, 12VDC

11

Maintenance

Summary of Contents for XG6500

Page 1: ...www generac com or 1 888 436 3722 Owner s Manual XG Series 6 500 8 000 Watt Portable Generator MODELS 005796 0 XG6500 005797 0 XG7000 005798 0 XG7000E 005800 0 XG8000 005747 0 XG8000E...

Page 2: ...Adding Gasoline 9 2 8 To Start the Engine 10 2 8 1 Manual Recoil Starting 10 2 8 2 Electric Starting XG7000E XG8000E 11 2 9 Stopping the Engine 11 2 10 Low Oil Pressure Shutdown System 11 2 10 1 Resta...

Page 3: ...US SITUATION OR ACTION WHICH IF NOT AVOIDED WILL RESULT IN DEATH OR SERIOUS INJURY Indicates a hazardous situation or action which if not avoided could result in death or serious injury Indicates a ha...

Page 4: ...ds and barriers are in place before operating the generator Never handle any kind of electrical cord or device while standing in water while barefoot or while hands or feet are wet DANGEROUS ELECTRICA...

Page 5: ...NATIONAL BUILDING CODE available from the American Insurance Association 85 John Street New York N Y 10038 3 AGRICULTURAL WIRING HANDBOOK available from the Food and Energy Council 909 University Ave...

Page 6: ...ne at 1 888 775 6937 1 2 1 ASSEMBLING THE WHEEL KIT AND FRAME FOOT The wheel kit is designed to greatly improve the portability of the generator You will need the following tools to install the wheel...

Page 7: ...o reset circuit breaker to protect the generator against electrical overload 8 Circuit Breakers AC The 30 Amp receptacle is protected with a pair of push to reset circuit breakers to protect the gener...

Page 8: ...interval providing a two hour window to perform service When the hour meter is in the Flash Alert mode the maintenance message will always alternate with elapsed time in hours and tenths The hours wil...

Page 9: ...y and Health Administration OSHA regulations local codes or ordinances that apply to the intended use of the generator Please consult a qualified electrician electrical inspector or the local agency h...

Page 10: ...ading the unit Add up the total wattage of all electrical devices to be connected at one time This total should NOT be greater than the generator s wattage capacity The rated wattage of lights can be...

Page 11: ...minimum American Petroleum Institute API Service Class SJ SL or better Use no special additives Select the oil s viscosity grade according to the expected operating temperature also see chart Above 40...

Page 12: ...r use engine or carburetor cleaner products in the fuel tank as permanent damage may occur 2 8 TO START THE ENGINE Never start or stop engine with electrical devices plugged into the receptacles AND d...

Page 13: ...Y XG7000E XG8000E n Do not permit smoking open flame sparks or any other source of heat around a battery Wear protective goggles rubber apron and rubber gloves when working around a battery Battery el...

Page 14: ...the following Fuel System Air Induction System Fuel Tank Intake pipe manifold Fuel Cap Air cleaner Carburetor Ignition System Fuel Lines Spark plug Evaporative Control System Ignition module Carbon C...

Page 15: ...hose and oil fill plug to drain oil completely into a suitable container When oil has completely drained install oil drain cap and tighten securely Place a suitable container beneath the oil filter an...

Page 16: ...it for storage NEVER store engine with fuel in tank indoors or in enclosed poorly ventilated areas where fumes may reach an open flame spark or pilot light as on a furnace water heater clothes dryer o...

Page 17: ...charger included in the accessory box see the Charging a Battery section RUNNING THE GENERATOR DOES NOT CHARGE THE BATTERY The battery shipped with the generator has been provided fully charged To rep...

Page 18: ...tuck open or closed 12 Engine has lost compression 1 Turn Fuel shut off ON 2 Clean or replace air cleaner 3 Fill fuel tank 4 Drain fuel tank and fill with fresh fuel 5 Connect wire to spark plug 6 Rep...

Page 19: ...17 Notes...

Page 20: ...market parts not made supplied or approved by Generac You are responsible for contacting a Generac Authorized Warranty Dealer as soon as a problem occurs The warranty repairs should be completed in a...

Page 21: ...t repaired or replaced under the ECS warranty shall be warranted for the remainder of the period prior to the first scheduled replacement point for that part 4 Repair or replacement of any warranted e...

Page 22: ...nostics performed by individuals other than Guardian Generac authorized dealers not authorized in writing by Generac Power Systems Failures due but not limited to normal wear and tear accident misuse...

Page 23: ...c com or 1 888 436 3722 Manual del propietario XG Series Generador port til de 6 500 8 000 vatios MODELO 005796 0 XG6500 005797 0 XG7000 005798 0 XG7000E 005800 0 XG8000 005747 0 XG8000E 2A OS GARANT...

Page 24: ...11 Mantenimiento 11 3 1 Cronograma de mantenimiento 11 3 2 Especificaciones del producto 11 3 2 1 Especificaciones del generador 11 3 2 2 Especificaciones del motor 12 3 2 3 Informaci n sobre emision...

Page 25: ...ca una situaci n peligrosa o acci n que si no se evita podr a traer como resultado la muerte o un da o serio CUIDADO Indica una situaci n peligrosa o acci n que si no se evita puede traer como resulta...

Page 26: ...nerador Aseg rese que todas las cubiertas protecciones y barreras apropiadas se encuentren en su lugar antes de operar el generador No manipule ningun tipo de dispositivo el ctrico mientras est de pie...

Page 27: ...res c digos regulaciones o leyes pertinentes la informaci n publicada listada abajo puede usarse como gu a para la operaci n de este equipo Siempre consulte la revisi n m s reciente aplicable para el...

Page 28: ...888 775 6937 1 2 1 ENSAMBLAJE DE LA RUEDA El kit de la rueda est dise ado para mejorar en gran medida la portabilidad del generador Usted necesitar las siguientes herramientas para instalar el kit de...

Page 29: ...provisto con un interruptor de circuito de presionar para reiniciar con el fin de proteger al generador contra sobrecargas el ctricas 8 Interruptores de circuito AC El recept culo de 30 amps est prote...

Page 30: ...as est en el modo de alerta de destello Flash Alert el mensaje de mantenimiento siempre alternara con el tiempo transcurrido en horas y d cimos Las horas destellar n cuatro veces luego alternar con lo...

Page 31: ...o de CA en el panel de control del generador a trav s de un cable jumper Requerimientos especiales Puede haber regulaciones federales o estatales respecto a la salud y seguridad ocupacional OSHA c dig...

Page 32: ...del generador La potencia nominal de las luces puede leerse en las mismas bombillas La potencia nominal de las herramientas aparatos y motores normalmente se puede encontrar en la etiqueta de datos o...

Page 33: ...de la toma de aceite y retire la tapa Llene lentamente el motor con aceite a trav s de la abertura hasta que llege a su marca de lleno Deje de llenar ocasionalmente para revisar el nivel de aceite El...

Page 34: ...siga la misma secuencia de choke listada arriba NOTA Si el motor dispara pero no sigue funcionando tire la palanca de choke a Full Choke y repita las instrucciones de arranque IMPORTANTE No sobrecarg...

Page 35: ...panel de control cuando el generador vaya a usarse NOTA No use el cargador dem bater as por m s de 48 horas en una carga 3 1 CRONOGRAMA DE MANTENIMIENTO Siga los intervalos del calendario Se requiere...

Page 36: ...o negligencia del operador Para recibir el valor total de la garant a el operador debe hacer el mantenimiento del generador tal como se instruye en este manual Se necesitar hacer algunos ajustes perio...

Page 37: ...ado 3 3 6 REEMPLAZO DE LA BUJ A Use buj as Champion RC14YC o equivalentes Reemplace la buj a una vez al a o Esto ayudar a que el motor arranque con mayor facilidad y funcione mejor 1 Detenga el motor...

Page 38: ...de cidos durante el almacenamiento Los gases cidos pueden da ar el sistema de combustible de un motor durante el almacenamiento Para evitar problemas con el motor el sistema de combustible deber vacia...

Page 39: ...apropiados en exteriores lejos de las flamas abiertas Aseg rese de que el motor est fr o No fume en la cercan a ni encienda cigarro alguno Presione la v lvula de combustible del panel de control y ret...

Page 40: ...de combustible a ON 2 Limpie o reemplace el limpiador de aire 3 Llene el tanque de combustible 4 Drene y llene el tanque de combustible con gasolina fresca 5 Conecte el cable a la buj a 6 Reemplace l...

Page 41: ...17 Notas...

Page 42: ...epuestos falsos o del mercado negro no fabricados suministrados o aprobados por Generac Usted es responsable de contactar a un concesionario autorizado de garant a de Generac tan pronto se presente el...

Page 43: ...mer punto de reemplazo programado para aquella parte 4 La reparaci n o reemplazo de cualquier parte garantizada relacionada a las emisiones bajo esta garant a ECS deber realizarse sin costo alguno par...

Page 44: ...ferentes a los concesionarios autorizados por Guardian Generac que no est n autorizados por escrito por Generac Power Systems Fallas debido a pero no limit ndose a el uso y desgaste normal accidente m...

Reviews: