20
Owner’s Manual for Mobile Generator
General Information
The Generator page displays the following generator
data, in real time (press
▲
or
▼
to scroll).
•
Voltage (ph-N)
•
Voltage (ph-ph)
•
Frequency
•
Current (A)
•
Load ph-N (kW)
•
Total load (kW)
•
Load ph-N (kVA)
•
Total load (kVA)
•
Single phase power factors
•
Power factor average
•
Load ph-N (kvar)
•
Total load (kvar)
•
Accumulated load (kWh, kVAh, kvarh)
•
Loading scheme
•
Phase rotation
•
Nominal
•
Active configuration
NOTE:
The list above varies, according to generator
make, model, and features.
NOTE:
As possible, distribute electrical loads equally
among generator lines. Minor load imbalances (10% or
less) usually do not cause problems. When loading
generator, observe the load (amperage) on each line.
Alarms Page
Figure 2-10. Alarm Page
The Alarms page displays active warnings and active
alarms, including engine DTCs.
ECU DTC Page
Figure 2-11. ECU DTC Page—Current DTCs
The ECU Current DTC page displays active ECU DTCs.
Press
►
to view previous ECU DTCs.
NOTE:
See engine manual for information on ECU DTCs.
NOTE:
All DTCs display on the ECU DTC page. Some
DTCs may also display in the Event Log, with similar
descriptions as those displayed on the ECU DTC page.
Event Log Page
Figure 2-12. Event Log Page
The Event Log page displays current and previous
alarms.
•
Event Log capacity is 250 alarm events. After 250
events are logged, each new event overwrites the
oldest.
•
Only alarms are logged.
•
Newest event displays at top of log; oldest at bottom.
010423
010424
010425
Summary of Contents for MMG35DF4
Page 28: ...24 Owner s Manual for Mobile Generator General Information This page intentionally left blank ...
Page 40: ...36 Owner s Manual for Mobile Generator Operation This page intentionally left blank ...
Page 48: ...44 Owner s Manual for Mobile Generator Troubleshooting This page intentionally left blank ...
Page 59: ......