26
Owner’s Manual for Mobile Generator
Operation
to cool. Pressing the ENTER (
) button will clear
the alarm and reset the controller.
NOTE:
Engine preheat is controlled by the ECU.
4. When the engine starts, it accelerates to operating
speed. If the Low Speed Idle switch is ON, the
engine accelerates to the low idle speed set-point.
IMPORTANT NOTE:
Allow the engine to warm for
approximately 10 minutes. Failure to properly warm the
engine prior to loading can cause premature engine wear
or failure.
5. When engine is warm, turn OFF the Low Idle
Speed switch.
6. Check the generator for excessive noise or
vibration and any coolant, oil, or fuel leaks before
applying any loads.
7. Verify the AC output voltage is correct. See
Fine
Voltage Adjustment
.
8. Verify generator frequency (Hz) is correct on the
generator screen. The frequency should be the
rating specified on the unit data tag.
9. If all wiring connections have been made correctly,
switch the main circuit breaker to ON (I), and then
add any loads attached to the receptacles by
switching the respective circuit breaker to the ON
(I) position. A slight change in engine sound when
a load is applied to the unit is normal.
AUTO (Remote) Starting the Unit
AUTO mode allows the operator to start and stop the unit
by closing the remote start contacts (on the lug panel),
programming a schedule stop sequence in the controller,
or through a telemetry signal (if equipped).
NOTE:
When in AUTO mode, the STOP button can be
pressed to stop the unit.
Review the
Pre-start Checklist
and
Manually Starting
the Unit
before putting the unit in AUTO mode. Follow all
safety warnings and review all information on isolating
the generator with a transfer switch if the unit is to be
used as a standby power supply. See
AUTO Exercise
Timer
, then proceed as follows:
1. Perform a manual start of the unit at least once to
verify the engine and generator are operating
correctly.
2. To check the remote start circuit, remove the wires
from the remote start terminal block. Press the
AUTO button, and the display screen will show
auto mode at the bottom of the screen.
3. Attach a jumper wire (minimum 16 gauge) across
the two terminals on the remote start terminal
block. This applies a ground to the controller to
close the starting circuit contacts. The engine will
crank, start, and run.
4. Remove the jumper wire from the remote start
terminal block and the engine runs the
stop
sequence. Reconnect any necessary wires from
the remote start switch (transfer switch) to the
remote start terminal block.
5. Verify the unit is in AUTO mode. The display
screen should show AUTO mode at the top of the
screen.
6. Switch the main circuit breaker ON (I).
7. Secure the unit by closing and locking all access
doors.
8. The unit is now ready for remote starting.
See
Figure 3-1
. The remote start terminal block provides
a connection for installation of a remote start switch
which will allow the unit to be started by a remote dry-
contact closure switch. For location of the remote start
terminal block, see
Figure 2-5
.
Before entering AUTO mode, verify the contacts on any
remote switch linked to the unit are open. If the contacts
on a remote switch are closed, the engine will crank and
start when AUTO mode is entered. Attach the switch
leads to the two unused terminals (A) on the unit’s
remote start terminal block.
Figure 3-1. Remote Start Terminal Block
Low Idle Switch
Engine idle speed is 1,000 to 1,200 rpm. The engine will
start at idle speed and run at idle for 15 seconds no
matter what position the idle switch is in. After 15
seconds of running at idle, the unit will ramp up to 1,800
rpm if the idle switch is OFF. Otherwise the unit will
continue to idle if the idle switch is ON.
When the engine is at idle speed (1,000 rpm), the voltage
regulator will not function and the output voltage is
dropped out by the voltage regulator.
IMPORTANT NOTE: Do not apply load to the unit
when the engine is running at idle speed.
Wet Stacking
The unit is powered by a diesel engine. Diesel engines
are susceptible to wet stacking if lightly loaded. Wet
stacking occurs when an engine is run at less than 30%
002806
A
Summary of Contents for MMG35DF4
Page 28: ...24 Owner s Manual for Mobile Generator General Information This page intentionally left blank ...
Page 40: ...36 Owner s Manual for Mobile Generator Operation This page intentionally left blank ...
Page 48: ...44 Owner s Manual for Mobile Generator Troubleshooting This page intentionally left blank ...
Page 59: ......