For the Output wiring instruction art. 5951 06
you should consult the technical data sheet of
the limit switch box art. 5987.
7. Breakdown view
8. Starting Up (Settings)
Note: The positioner leaves the factory set to position 0º and path 90º. In case you
need to establish these settings, proceed as follows.
8.1 Zero Setting
•
Send a run start signal (4 mA).
•
Turn the ZERO setting wheel clockwise or counter-clockwise until the reference
lines of the indicator cam and the tangent point of the bearing match.
ZERO