In the case of the single effect actuator, check that it is set to zero point at
standard pressure. Otherwise, repeat Zero Setting.
8.2 Span Setting
•
Set the span so that the actuator stops at position 0% in the run with an input
signal of 0% (4 mA), and so that it stops at position 100% with an input signal of
100% (20 mA), respectively.
•
Check Zero point and repeat the Span setting as many times as required.
•
Once the equipment is set, tighten the Locking screw.
8.3 Auto / Manual Switch
This switch is used to switch between Auto and Manual modes. The equipment leaves
the factory in Auto mode. To switch to Manual mode, turn the A/M regulator counter-
clockwise.
In Manual mode, the network pressure connects directly to the actuator. Return to Auto
mode after using.
This option does not apply to the single effect actuator connected to output OUT2.