13 

8.6.4  Feedback signal 25% (8 mA) position adjusting 
The valve locate in feedback 25% (8 mA) position. 

Press the “+” button or “-“button , 

adjust the current value

, then press the “enter” button. 

Observe the amperemeter value:  if the amperemeter value jump from 8 mA to 12 mA 
around, means the feedback signal 25% (8 mA) position confirmed. Module waiting for 
the feedback signal 50% (12 mA) position confirm. 
 
 
8.6.5  Feedback signal 50% (12 mA) position adjusting 
The valve locate in feedback 50% (12 mA) posit

ion. Press the “+” button or “-“button , 

adjust the current value

, then press the “enter” button. 

Observe the amperemeter value:  if the amperemeter value jump from 12 mA to 16 mA 
around, means the feedback signal 50% (12 mA) position confirmed. Module waiting for 
the feedback signal 75% (16 mA) position confirm. 
 
 
8.6.6  Feedback signal 75% (16 mA) position adjusting 
The valve locate in feedback 75% (16 mA) posit

ion. Press the “+” button or “-“button , 

adjust the current value, then press 

the “enter” button. 

Observe the amperemeter value:  if the amperemeter value jump from 16 mA to 20 mA 
around, means the feedback signal 75% (16 mA) position confirmed. Module waiting for 
the feedback signal 100% (20 mA) position confirm. 
 
 
8.6.7 Feedback signal 100% (20 mA) position adjusting 
The valve locate in feedback 100% (20 

mA) position. Press the “+” button or “-“button , 

adjust the current value

, then press the “enter” button. 

Observe the amperemeter value:  the amperemeter value should be reduce at first, after 
the value stable, it will comeback to 20mA, at the same time, the indicator light on module 
will flash some times. 
 
After finished step 8.6.7, the module automatic enter normal run state 
 

 
 

9. Maintenance 

 

Even though this equipment requires no maintenance, it is recommended to carry out 
regular inspections, which must include: 
 

  Verifying the mounting / alignment of the actuator and the positioner. 

  Verifying the electrical connection of the signal. 

  Making sure all bolts are present and tightened. 

  Verifying the state of the filters of the air installation to ensure that good quality air 

reaches the equipment. 

 

Summary of Contents for 5951 00

Page 1: ...italet de Llobregat Barcelona Spain genebre genebre es www genebre es GENEBRE S A UPDATE DATE 27 05 2021 UPDATE NUMBER 4 1 INSTALLATION OPERATION AND MAINTENANCE MANUAL Electro Pneumatic Positioner fo...

Page 2: ...Storage Conditions 5 5 Preliminary Checks 5 6 Positioner Installation 5 6 1 Installation of the Support and the Positioner on the actuator 5 6 2 Mounting of the Cam 6 6 3 Air Connection 7 6 4 Electri...

Page 3: ...r single effect actuators Easy setting of zero and of the trajectory Easy switching of direction clockwise counter clockwise Low air consumption and easy connection to air ducts 2 Data and Technical F...

Page 4: ...must be familiar with all notices and warnings described in these instructions Not complying with these notices and warnings may cause serious personal injury and material damages Certain parts of the...

Page 5: ...Avoid placing them straight on the floor Use pallets shelves o wood bases Genebre S A recommends to visually examine the possible damages suffered during transportation and storage Visual inspection m...

Page 6: ...eaves the factory with the cam mounted on the shaft and the indicator plate in the position RA counter clockwise reverse acting In case you need to switch the direction clockwise direct acting proceed...

Page 7: ...UPDATE NUMBER 4 7 Fix the cam using the upper nut so that the reference line 0 is tangent to the bearing Once the cam is mounted place and fix the indicator plate to the main shaft using the M3 screw...

Page 8: ...uit completely to avoid strange particles 3 In applications with single effect actuator spring return close output OUT1 or OUT2 as appropriate 6 4 Electrical Connection transmission signal Connect the...

Page 9: ...nsult the technical data sheet of the limit switch box art 5987 7 Breakdown view 8 Starting Up Settings Note The positioner leaves the factory set to position 0 and path 90 In case you need to establi...

Page 10: ...signal of 0 4 mA and so that it stops at position 100 with an input signal of 100 20 mA respectively Check Zero point and repeat the Span setting as many times as required Once the equipment is set ti...

Page 11: ...cillation due to mounting with a low air capacity actuator refer to section 8 5 8 5 Air throttle in pilot valve In case of low air capacity actuators there could be oscillation in the equipment render...

Page 12: ...e signal sent 4 20 mA 8 6 1 Connect 24VDC power source series connect amperemeter convenient for observing the feedcack signal s current value Observe the value of the amperemeterr it must be between...

Page 13: ...The valve locate in feedback 75 16 mA position Press the button or button adjust the current value then press the enter button Observe the amperemeter value if the amperemeter value jump from 16 mA to...

Page 14: ...r flow hole located on the A M regulator to remove any particles that might be left inside Cleaning the A M Switch Finally clean the A M Switch regulator using air and place it back in the enclosure D...

Reviews: