Connect terminals 13 – 18 to the normally open pump start and stop float switches based on the pumping 
operation (i.e. pump down).    
 
Connect terminals 19 and 20 to the normally open LOW level float switch.    
 

OPERATING INSTRUCTIONS 

 
Hand-Off-Automatic selector switches may be provided for the pumps allowing them to be operated automatically 
or manually.  To energize the pumps, turn the respective switch to the “Hand” position.  To de-energize the 
pumps, turn the respective switch to the “Off” position.  These switches will normally be in the “AUTO” position 
and operation will then be as follows.  
 
The panel is equipped with an automatic pump alternator.  The pumps will alternate when the lead pump stops 
beginning with pump #1.  When the level rises to lead pump electrode or float pump #1 will energize.  When the 
level recedes to the pump stop(s) electrode or float the alternator will sequence to pump #2.  On the next lead 
pump start pump #2 will energize.  Should both pumps be required then both pumps will energize and the cycle 
will reset to pump #1. 
 

Pump Down 

The lead pump will be started when the tank level rises to the lead pump START electrode or float and will 
continue in operation until the level is reduced below pump(s) STOP electrode or float. 
 
Should the pump be unable to meet the demand or fail completely and the level rises to the lag pump START 
electrode or float, the lag pump will be started and will continue in operation until the level is reduced below 
pump(s) STOP electrode or float. 
 

Pump Up 

The lead pump will be started when the tank level recedes below the lead pump START electrode or float and will 
continue in operation until the level rises to the pump(s) STOP electrode or float. 
 
Should the pump be unable to meet the demand or fail completely and the level recedes below the lag pump 
START electrode or float, the lag pump will be started and will continue in operation until the level rises to the 
pump(s) STOP electrode or float. 
 

High Alarm 

If the tank level rises to the HIGH LEVEL electrode or float, the high level alarm light will illuminate. 
If the audible alarm option was chosen the following will also occur: 
 
The audible alarm horn will sound and the contacts connected to terminal pair 7 – 8 will close.   The contact will 
remain closed until the high level condition is corrected.  The audible alarm can be silenced by momentarily 
depressing the SILENCE pushbutton, however, the light will remain on until the abnormal condition is corrected. 
 

Low Alarm 

If the tank level rises to the LOW LEVEL electrode or float, the low level alarm light will illuminate. 
If the audible alarm option was chosen the following will also occur: 
 
The audible alarm horn will sound and the contacts connected to terminal pair 9 – 10 will close.   The contact will 
remain closed until the high level condition is corrected.  The audible alarm can be silenced by momentarily 
depressing the SILENCE pushbutton, however, the light will remain on until the abnormal condition is corrected. 
 
 