V - COMMISSIONING

1 - FILLING THE INSTALLATION WITH WATER 

- Filling the installation:

• before you fill, rinse the installation's pipes, 

except for the tank.

Refer to the boiler's manual

- Filling the tank:

• fill the domestic hot water production system 

using the installation's safety control box (8, 
fig. 9 - page 19 - chapter IV - INSTALLATION) 
taking care to open a hot water tap.

• After the system is full, check that the tank's 

access flap is tightly shut.

- Drain the tank and the installation thoroughly 

before filling. 

2 - VERIFICATIONS PRIOR TO COMMISSIONING 

- Check that the tank access flap is tight and 

waterproof (8, fig. 2 - page 8 - chapter III - 
TECHNICAL SPECIFICATIONS,

- Check the waterproofing of the various seals and 

connectors in the installation,

- Check that the primary circuit is drained,

- Check that the electrical connection is correct.

- To guarantee the stated performances, check 

that the security control box's cold water tap is set 
to obtain a maximum flow rate for the hot water of 
the value indicated in section 1 -  page 6 - 
chapter III - TECHNICAL SPECIFICATIONS).

3 - USER INFORMATION

The installer must train the user in how the 
appliance works. In particular, the user must be 
informed of the role and operation of the safety 
mechanisms and the need to have the appliance 
maintained regularly by a qualified professional.

WARNING TO THE USER

Do not remove or adjust any component part of 
unvented water heater :contact the installer.

If this unvented water heater develops a fault, such 
as flow of hot water from the discharge pipe, switch 
the heater off and contact the installer.

Summary of Contents for EBS-1 100

Page 1: ...FOLLOW COMMISSIONING INSTRUCTIONS OBSERVE THE WARRANTY CONDITIONS READ THE W HOLE MANUAL CAREFULLY NO SAFETY DISCHARGE TO BE REDUCED IN SIZE CONDENSE TO BE 32 m m PVC I N S T R U C T I O N S High fide...

Page 2: ...TUBE INSULATION 10 3 FITTING THE IMMERSION HEATER KIT 10 4 SELECTIVE VALVE KIT EBS 1 CONNECTION WITH A THI C OR ZEM C BOILER OPTION 11 5 SELECTIVE VALVE KIT EBS 1 CONNECTION WITH A ZEM C BOILER OPTIO...

Page 3: ...P T VALVE 24 4 CHANGING THE THERMOSTATS OR THE THERMOMETER 25 4 1 Bulbs positioned in the pocket 7 25 4 2 Bulb positioned in the pocket D 25 4 3 Changing the thermostats or the thermometer 25 VII PAR...

Page 4: ...ls and accessories that benefit from a sanitary conformity certifica te for domestic water distribution circuits Never place the insulation valve between the safety control box and the tank Respect th...

Page 5: ...anger an access flap polystyrene insulation that can be easily removed a domestic hot water temperature adjustment thermostat a thermometer a water overheating safety thermostat 90 C a 7 bar P T valve...

Page 6: ...ontinuous flow rate mCE 0 021 0 021 0 074 0 080 Primary flow rate l h 1249 1249 1895 1964 Maximum domestic hot water storage temperature C 80 Domestic hot water temperature safety thermostat C 90 Tank...

Page 7: ...7 TECHNICAL SPECIFICATIONS 2 DIMENSIONS EBS 01 3E 297 297 600 A 30 782 Fig 1 Models EBS 1 100 EBS 1 150 EBS 1 200 EBS 1 300 A 795 1020 1245 1695 Top view...

Page 8: ...d water inlet 6 Hot water tank 7 Pocket for domestic hot water setting thermostat bulb 8 Access flap 9 Domestic hot water temperature setting thermostat 10 Thermometer 11 Stainless steel coiled pipe 1...

Page 9: ...s flow rate at 40 C Specific flow rate Heating time at 60 C 1 Load time Drawable volume at 40 C in 10 min Drawable volume at 40 C in 1 hour Drawable volume at 40 C in 10 min Drawable volume at 40 C in...

Page 10: ...intake weld B below the tank put it in the required position to connect the cold water intake Screw the cold water intake tube 12 2 onto the elbow 12 1 by running it through one of the openings provi...

Page 11: ...ion of the EBS 1 with the THI C or ZEM C boilers Refer to the kit assembly instructions ref W07 31709 5 SELECTIVE VALVE KIT EBS 1 CONNECTION WITH A ZEM C BOILER OPTION The selective valve kit enables...

Page 12: ...valve and check that it discharges water Open expansion relief valve and check that it discharges water Check operation of all controls Every two years the following additional mainte nance should al...

Page 13: ...d kit and flush through the tank to the drain by using a hose through the inspec tion door This unit is only to be used with our oil or gas boiler with a thermostatic control It should not be used wit...

Page 14: ...the Safety shut off zone valve Safety Discharge Pipe from Tundish See Table 2 below for sizing details of safety dis charge pipe from our tundish Worked example The example below is for a G 1 2 temper...

Page 15: ...if it is required to replace the unvented kit it is not necessary to drain all tank Please find below how to install the unvented kit 6 3 1 Unvented kit for EBS 1 cylinders 6 3 2 Unvented kit for EBS...

Page 16: ...cylinders 1 Unvented kit 2 Safety zone valve 3 Expansion vessel 4 Expansion vessel connection 5 Tundish 1 2 3 4 5 4 7 6 9 12 11 10 4 Expansion vessel connection 6 Cold water 7 Cold water to EBS 1 tank...

Page 17: ...tlet 5 Mains cold water supply inlet via unvented kit 9 Domestic hot water temperature setting thermostat 16 Pressure and temperature relief valve 17 High limit cut off thermostat 18 P T valve drain 1...

Page 18: ...native It is strictly subject to local Dispensation and approval must be sought from NHBC and Building Control inspector prior to installation 1 22 mm copper discharge pipe 2 Tundish visible point off...

Page 19: ...essories to connect install or adjust 6 5 Hydraulic diagram 5 3 8 9 10 7 1 2 3 4 14 1 2 6 5 12 11 EBS 08 3E 13 4 16 15 Fig 9 1 Primary inlet boiler to tank 2 Domestic hot water outlet 3 Domestic hot w...

Page 20: ...pply must contain a circuit breaker preferably bipolar with a 6 A trip switch or fuse Respect the Live Neutral polarities 7 1 1 Boiler with domestic hot water load pump The thermostat 9 fig 10 starts...

Page 21: ...afety thermostat bulb 17 as far as possible in the pocket 7 to ensure satisfactory thermal contact drill a hole in the upper thermoformed base run the domestic hot water sensor bulb delivered with the...

Page 22: ...e various seals and connectors in the installation Check that the primary circuit is drained Check that the electrical connection is correct To guarantee the stated performances check that the securit...

Page 23: ...tion system Always set to a value greater by at least 10 C than the desired storage temperature in the domestic hot water production system but never to a value of over 85 C to avoid any unplanned tri...

Page 24: ...ker above 60 C If the tank is inspected through the access flap 8 fig 13 provided for the purpose remove the protective plate 22 remove the 3 screws 23 remove the insulation 18 remove the access flap...

Page 25: ...p from the safety thermostat 17 unscrew the attachment screw on the thermostat 17 remove the defectives thermostats 9 17 and replace it position the bulbs in the pocket 7 Push the safety thermostat bu...

Page 26: ...26 VII PARTS LIST EBS 1 100 150 200 300...

Page 27: ...8 1935X440 BS100 15 A90 16623 ABS SHEET EP 0 8 1935X665 BS150 15 A90 16624 ABS SHEET EP 0 8 1935X890 BS200 15 A90 16625 ABS SHEET EP 0 8 1935X1340 BS300 16 D20 16720 HALF SHELL INSULATION IN POLYSTYRE...

Page 28: ...iption Vt Total volume of the tank Vu Useful volume of the tank Vech Internal volume heat exchangers Pn ech Rated power heat exchangers T max Maximum domestic hot water storage temperature PMS Maximum...

Page 29: ...equivalent d Maintenance must be carried out annually by a qualified company from the first year of use The warranty excludes all compensation for any reason whatever The warranty is not applicable i...

Page 30: ...30 NOTES...

Page 31: ...31 NOTES...

Page 32: ...please contact Evinox Ltd Blenheim House 1 Blenheim Road Epsom Surrey KT19 9AP el ax e mail T 44 0 1372 722277 F 44 0 1372 744477 www evinox co uk Company number 4404137 sales evinox co uk technical...

Reviews: