- 21 -
INSTALLATION
7.1.2 - Boiler equipped with electronic
regulation
The domestic hot water temperature will be adjusted
on the boiler's regulator. (In this application the
setting thermostat (9) is not required as the
temperature is set by the electronic control of the
boiler).
- remove the setting thermostat bulb (9) and set to
one side (see the picture fig. 11),
- remove the safety thermostat bulb (17) and the
thermometer bulb (10) from the pocket (7) -
access from the top of the tank (fig. 11).
- push the safety thermostat bulb (17) as far as
possible in the pocket (7) to ensure satisfactory
thermal contact.
- drill a hole in the upper thermoformed base.
- run the domestic hot water sensor bulb delivered
with the boiler through this opening,
- position the domestic hot water sensor bulb in the
pocket (7).
- Reposition the thermometer bulb as far as
possible into the pocket (D) planned for this
purpose in the polystyrene insulation.
The bulb of the safety thermostat (17)
will always be inserted in the pocket (7)
before the bulb of the domestic hot
water sensor.
Leave the setting thermostat (9) on
"Maximum" when tank is heated by a
boiler.
!
9
10
D
D
E
B
S
-15-3E
17
22
23
18
7
21
C
9
EBS-1
1
-3E
17
10
Fig. 11
10
9
7