11.0 - RELAY OUTPUT CONNECTIONS

The maximum relay contact capacity is 2A at 28Vdc; to actuate devices having
a higher absorption rate, an auxiliary relay must be provided.

!

For safety reasons, always insert a protection fuse (3-4A max.)

between the device to be managed and the detector contacts.

PAGE 08 - INSTALLER MANUAL

12.0 - CIRCUIT DIAGRAM

13.0 - CORRECT POSITION FOR LPG DETECTION

INSTALLER MANUAL - PAGE 09

The detector must be installed at about 20-40cm from the floor as illustrated

here below.

Min 1 meter

Max 5 meter

20/40 cm

Model 911

M1
M2

SL1

P1

- Screw-type terminal block to connect alarm output contact.
- Push-button type terminal block for 12V or 24V.

- Voltage switch 12 or 24V.

- Sensitivity level selector.

Alarm
output

Card fixing

screw

Summary of Contents for 911

Page 1: ... com Reg n 532 A AC 2782UK Rev 00 12 09 UK INSTALLATION AND USE MANUAL INSTALLATION CERTIFICATE The undersigned qualified installer attests to have personally fitted the here described detector on the following vehicle according to the manufacturer s instructions By Sold on Type of device Vehicle Narcotic Gas and Explosive Wireless Detector Gas 911 911 ...

Page 2: ...ave any effect on the occupants N B In compliance with European standard En50194 the detector can signal the presence of explosive gas LP when its concentration is higher than 10 of the LEL Lower Explosive Limit the minimum concentration which can cause an explosion The 911 detector also activates the output relay which actuates other devices ex cabin lights vehicle horn etc to discourage anyone t...

Page 3: ...alarm device The relay supplies the contacts NC C NO on the terminal block M1 see connection example in par 11 5 0 SELF DIAGNOSIS The detector is provided with an acurate and reliable self diagnosis system which continuously checks its performance and efficiency any failure or the exhaustion of the probe after a life cycle of more than 11 000hrs is signaled by the yellow LED turning ON and by a wa...

Page 4: ... introduce the cables which must have a section comprised between 0 5 and 1 5 mm Remove 9mm of sleeve from the cable before inserting it in the terminal block release the push button and pull on the cable to make sure it is well secured The auxiliary devices conductors intended to manage the alarm must be connected to terminal block M1 the maximum rating of the relay contacts is 2A at 28Vdc refer ...

Page 5: ...the detector contacts PAGE 08 INSTALLER MANUAL 12 0 CIRCUIT DIAGRAM 13 0 CORRECT POSITION FOR LPG DETECTION INSTALLER MANUAL PAGE 09 The detector must be installed at about 20 40cm from the floor as illustrated here below Min 1 meter Max 5 meter 20 40 cm Model 911 M1 M2 SL1 P1 Screw type terminal block to connect alarm output contact Push button type terminal block for 12V or 24V Voltage switch 12...

Page 6: ... casing and inflammability class Approximate weight Relay contact rating APPROPRIATE CONTAINERS ONLY 15 0 WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT DIRECTIVE WEEE In the European Union this label indicates that this product must not be disposed of with household waste It should be deposited at an appropriate facility to enable recovery and recycling Directives 2002 95 CE 2002 96 CE and 2003 108 CE...

Reviews: