Item Identification

Part Number

T8060*

T8070*

T8080*

T8090

T8100

T8110

T8120*

T8130

T8140

T8150

T8160

T8170

T8180*

T8190*

T9060**

T9070**

T9080**

T9090**

T9100**

T9110**

T9120**

T9130**

T9140**

T9150**

T9160**

T9170**

T9180**

T9190**

Centigrade       

º

C +/-5

º

60

70

80

90

100

110

120

130

140

150

160

170

180

190

Fahrenheit           

º

F +/-9

º

140

158

176

194

212

230

248

266

284

302

320

338

356

374

Identifying 

wire colors

White / 

Gray

White / 

Brown

White / 

White

Green / 

Green

Red / Red

Brown / 

Brown

Grey / 

Grey

Blue / 

Blue

White / 

Blue

Black / 

Black

Blue / 

Red

White / 

Green

White / 

Red

Black / 

Grey

*Consult factory - Non-stocked temperatures.  Consult factory for mimimums

**Consult factory - Special order item.  Consult factory for mimimums

Switching temperatures (Nominal)

Summary of Contents for Motogard 120 Series

Page 1: ...Over Temperature Protection System Installation Instructions Motogard...

Page 2: ...PTC Thermistors to indicate when the equipment has exceeded the set temperature These Thermistors act as a switch which when reaching the pre selected temperature will cause the resistance to increas...

Page 3: ...sing less than 6 Thermistors Any unused input Install a 150 Ohm 1 2W resistor from sensor common terminal 5 to any unused input Output Load Connections 1 With power applied to the controller and all i...

Page 4: ...mum number of Thermistors in parallel Three 3 4 Note If using less than 3 Thermistors Any unused input Install a 150 Ohm 1 2W resistor from sensor common terminal 5 to any unused input Output Load Con...

Page 5: ...istors in parallel Three 3 4 Note If using less than 3 Thermistors Any unused input Install a 150 Ohm 1 2W resistor from sensor common terminal 9 to any unused input Output Load Connections 1 Terminal...

Page 6: ...terminals 3 and 4 should be between 150 Ohm to 500 Ohm in ambient conditions If the resistance measures less than 150 Ohms a 150 Ohm 1 2W resistor should be installed in series with the Thermistors to...

Page 7: ...060 T9070 T9080 T9090 T9100 T9110 T9120 T9130 T9140 T9150 T9160 T9170 T9180 T9190 Centigrade C 5 60 70 80 90 100 110 120 130 140 150 160 170 180 190 Fahrenheit F 9 140 158 176 194 212 230 248 266 284...

Page 8: ...1500 ohms or more Controller ON with 500 ohms or less OFF with approx 1500 ohms or more Controller ON with 150 to 500 ohms OFF with approx 1500 ohms or more Controller ON with 150 to 500 ohms OFF wit...