Series 135 Motogard

The Series 135 Motogard is designed to take in up 
to 3 Thermistors wired in Parallel, and has a Form C 
Mechanical Output relay.

Connections

Power Connections:

The 135 Series Motogard relay is designed to operate 
off of /-10%, Single Phase, 50/60Hz.
Connect 120VAC to input terminals 1 and 2.

Thermistor Connections:

1.  Connect one lead of each Thermistor to terminals 

6, 7, and 8 respectively.

2.  

Connect other leads of each Thermistor to 
Common terminal 9.

3.  

Maximum number of Thermistors in parallel: 

 

Three (3)

4.  Note:  If using less than 3 Thermistors.  Any 

unused input – Install a 150 Ohm 1/2W resistor 
from sensor common (terminal 9) to any unused 
input.

Output Load Connections:

1.  Terminals 3, 4 and 5 comprise a set of “Form C” 

contacts with terminal 4 common, Terminal 5 is 
the open side and terminal 3 is the closed side.  

2.  Be sure power is never applied directly across the 

contact but always in series with the load.  

3.  Maximum allowable load – 5 Amps at 120/240VAC 

or 28VDC.

4. 

 

The closed output of the Motogard Over 
temperature Protection System has been 
specifically designed to operate directly in series 
with most main line contactors.  If contact current 
is greater than 5 Amps  at 115VAC, an interposing 
relay must be used.  

5.  The open output of the Series 135 relay can be 

used for trip indication.

Summary of Contents for Motogard 120 Series

Page 1: ...Over Temperature Protection System Installation Instructions Motogard...

Page 2: ...PTC Thermistors to indicate when the equipment has exceeded the set temperature These Thermistors act as a switch which when reaching the pre selected temperature will cause the resistance to increas...

Page 3: ...sing less than 6 Thermistors Any unused input Install a 150 Ohm 1 2W resistor from sensor common terminal 5 to any unused input Output Load Connections 1 With power applied to the controller and all i...

Page 4: ...mum number of Thermistors in parallel Three 3 4 Note If using less than 3 Thermistors Any unused input Install a 150 Ohm 1 2W resistor from sensor common terminal 5 to any unused input Output Load Con...

Page 5: ...istors in parallel Three 3 4 Note If using less than 3 Thermistors Any unused input Install a 150 Ohm 1 2W resistor from sensor common terminal 9 to any unused input Output Load Connections 1 Terminal...

Page 6: ...terminals 3 and 4 should be between 150 Ohm to 500 Ohm in ambient conditions If the resistance measures less than 150 Ohms a 150 Ohm 1 2W resistor should be installed in series with the Thermistors to...

Page 7: ...060 T9070 T9080 T9090 T9100 T9110 T9120 T9130 T9140 T9150 T9160 T9170 T9180 T9190 Centigrade C 5 60 70 80 90 100 110 120 130 140 150 160 170 180 190 Fahrenheit F 9 140 158 176 194 212 230 248 266 284...

Page 8: ...1500 ohms or more Controller ON with 500 ohms or less OFF with approx 1500 ohms or more Controller ON with 150 to 500 ohms OFF with approx 1500 ohms or more Controller ON with 150 to 500 ohms OFF wit...

Reviews: