background image

INSTALLATION INSTRUCTIONS

Temperature and Pressure-Relief Valve

DO NOT

  plug  the  temperature  and  pressure-relief 

valve or its discharge line. 

DO NOT

 remove the relief 

valve.  Make  sure  the  relief  valve  is  properly  sized 

for  the  water  heater.  If  the  relief  valve  continuously  

discharges water, call a qualified service technician to 

correct the problem. Failure to follow these instructions 

can result in property damage, personal injury, or death.

To protect from excessive pressure and/or tempera-

ture, the manufacturer has installed a temperature and  

pressure-relief valve that meets the requirements of 

the  Standard  for  Relief  Valves  and  Automatic  Gas 

Shut-Off  Devices  for  Hot  Water  Supply  Systems, 

CSA 4.4 in Canada and ANSI Z21.22 in the United 

States. This relief valve has a maximum set pressure  

that  does  not  exceed  the  hydrostatic  working  pres-

sure of the water heater (150 psi = 1,035 kPa) and a 

BTUH rating equal to or greater than the input rating, 

as  shown  on  the  water  heater  rating  plate.  It  should 

never be plugged or removed from the opening marked 

for it on the water heater. 

If  this  relief  valve  should  need  to  be  replaced,  use 

only  a  new  temperature  and  pressure-relief  valve. 

Never install an old or existing relief valve as it may be 

damaged or inadequate for the working requirements 

of the new water heater. This new relief valve must 

meet  all  local  codes  or,  at  a  minimum,  the  require-

ments  listed  above.  Never  install  any  other  type  of 

valve between the relief valve and the water heater.
A  discharge  line  must  be  installed  into  the  relief 

valve. The discharge line:

•  Must not be smaller than the outlet pipe size of the 

relief valve. 

•  Must  not  terminate  less  than  six  (6)  inches  (15.2 

cm)  and  not  more  than  twelve  (12)  inches  (30.5 

cm) above a floor drain.

•  Must not be restricted in any way. Do not thread, 

cap, or in any way restrict the end of this outlet.

•  Must  be  of  a  material  capable  of  withstanding 

210

o

F (99

o

C) without distortion.

•  Must be installed to allow complete drainage of the 

relief valve and discharge line.

•  Must terminate at an adequate free-flowing drain. 

8

  1)  Vent pipe

  2)  Drafthood

  3)  Union

  4)  Cold water  

 

manual shut-off valve

  5)  Cold water inlet

  6)  Expansion tank

  7)  Temperature  

 

& pressure-relief valve

  8)  Overflow tube

  9)  Drain valve

10)  Combustion 

 

air intake holes

11)  Drain pan

12)  Free-flowing floor drain

13)  Sight glass

14)  Resettable 

 

thermal switch

15)  Inner access door

16)  Outer access door

17)  Cap

18)  Drip leg (Sediment trap)

19)  Gas supply 

 

manual shut-off valve

20)  Union

21)  Gas control valve

22)  Rating plate

23)  Piezo igniter

24)  Dip tube

25)  Hot water outlet

26)  Union

27)  Burner

28)  Main burner orifice

29)  Pilot

30)  Thermocouple

31)  Electrode

Figure 8

1

2

5

6

3

4

24

7

8

23

9

10

11

12

16

15

14 13

20

17

18

19

21

22

25

26

27

29

31

30

28

Minimum Slope

1/4”/foot (21mm/m)

WARNING

DANGER

Summary of Contents for GE-IM016En-0312

Page 1: ...sing property damage personal injury or death DO NOT store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS DO NOT try...

Page 2: ...f an FVIR technology equipped water heater due to a flammable vapour shutdown is not covered under the terms of the Standard Basic Limited Warranty Safety Information 3 Installation Instructions 4 Loc...

Page 3: ...tial hazards that can kill or hurt you and others All safety messages will follow the safety alert symbol and either the word DANGER or WARNING Serious injury or death can occur if you do not follow t...

Page 4: ...hteen 18 inches 45 7 cm from the top see Figure 1 Combustion and Ventilation Air Supply In order for the water heater to operate properly it must be supplied with an uninterrupted flow of clean com bu...

Page 5: ...eans of a duct This duct shall be sized accord ing to CAN CSA B149 1 and terminate within 1 foot above and within 2 feet horizontally from the burn er level of the appliance having the largest input I...

Page 6: ...eing highly flam mable become highly corrosive acid compounds when burned Exposure to such compounds can be hazardous and lead to premature product failure Should the water heater fail due to exposure...

Page 7: ...not exceed 75 of the vertical vent height in no case exceeding 20 feet 6 1 m All horizontal runs must have a minimum rise of 1 4 inch per foot 21 mm m of run See Figure 8 All joints must be securely...

Page 8: ...nts of the new water heater This new relief valve must meet all local codes or at a minimum the require ments listed above Never install any other type of valve between the relief valve and the water...

Page 9: ...tional Fuel Gas Code ANSI Z223 1 in the United States Only new piping with cleanly cut threads may be used together with a suitable sealing compound that is approved for natural and propane gases It i...

Page 10: ...an the potable water heating system 5 Where water temperature in excess of 140o F 60o C is required for a space heating application a mixing valve must be installed in the potable side of the system T...

Page 11: ...manufacturer s supplied drafthood been installed correctly L Is the vent piping made of an approved material and sized correctly L Has the venting been installed with 1 4 inch rise per foot 21 mm m of...

Page 12: ...light any appliance DO NOT touch any electric switch DO NOT use any phone in your building From a neighbour s phone immediately call your gas supplier Follow the gas supplier s instructions 1 STOP Rea...

Page 13: ...decrease the temperature or coun terclockwise to increase the temperature The reference mark on the temperature dial indicated by a large triangle represents 130 F 54 C see Figure 9 Each mark to the...

Page 14: ...ass to examine the flames A soft blue flame indicates proper gas combustion A yellow tipped flame indicates poor combustion With a vacuum cleaner remove any dust lint and dirt accumulation on or aroun...

Page 15: ...ve 5 Connect one end of a garden hose to the water heater drain valve and put the other next to a free flowing drain 6 Open the drain valve by inserting a flat head screwdriver into the slot on the he...

Page 16: ...rain valve 7 Overflow tube 8 Baffle 9 Flue reducer 10 Drafthood 11 Anode 12 Dip tube 13 Temperature pressure relief valve 1 Burner 2 Inner door Part 1 3 Outer access door 4 Resettable thermal switch 5...

Page 17: ...ve The flame burns at the orifice Low gas pressure Check with gas utility company Defective gas control valve Replace with new gas control valve The pilot will not light or remain lit No gas Check wit...

Page 18: ...ater drips from the relief valve Heater stacking Lower gas control valve setting Excessive water pressure Install a pressure reducing valve Thermal expansion in a closed water system Install an expans...

Page 19: ...age caused by not having the water heater installed adjacent to a free flowing drain in the event of water leakage 10 If the heater is operated at water temperatures exceeding the maximum setting of t...

Page 20: ...___________________________________________________________ ________________________________________________________________________________ ___________________________________________________________...

Reviews: