background image

TROUBLESHOOTING GUIDE

18

CONDITION

CAUSE

REMEDY

High operating costs
(Continued)

Long runs or exposed piping.

Insulate piping.

Hot water piping on outside wall.

Insulate piping.

Insufficient hot water.

Low gas pressure.

Check with gas utility company.

Wrong piping connections.

Correct piping, dip tube must be in cold inlet.

Sediment or lime in tank.

Drain. Check to see if water treatment is necessary.

Water heater is undersized.

Install the size of water heater that meets the demand.

Gas control valve set too low.

Turn temperature knob to desired temperature.

Leaking  faucets.

Repair faucets.

Wasted hot water.

Advise consumer.

Long runs or exposed piping.

Insulate piping.

Hot water piping on outside wall.

Insulate piping.

Slow hot water recovery.

Insufficient secondary air.

Provide fresh air ventilation.

Low gas pressure.

Check with gas utility company.

Gas control valve set too low.

Turn temperature dial to desired temperature.

Improper calibration.

Replace gas control valve.

Flue clogged.

Clean. Check for source of trouble and correct.

Water heater is undersized.

Install size of water heater that meets demand.

Wrong piping connection.

Correct piping, dip tube must be in cold inlet.

Wasted hot water.

Advise consumer.

Leaking water.

Poorly sealed, hot or cold water connections,

gas control valve threads, relief valve,

or drain valve.

Tighten threaded connections. 

Leakage from plumbing system or 

other appliances.

Inspect plumbing system and other appliances.

Condensation.

Refer to Condensation.

Water drips from the
relief valve.

Heater stacking.

Lower gas control valve setting.

Excessive water pressure.

Install a pressure-reducing valve.

Thermal expansion in a closed water system.

Install an expansion tank.

Improperly seated valve.

Check relief valve works properly and 

replace if necessary.

The gas control valve fails
to shut-off.

Defective gas control valve.

Replace with new gas control valve.

Improper calibration.

Replace gas control valve.

Condensation.

Water heater filled for first time.

Let water heater warm up. Problem should go away. 

If it persists, check all plumbing connections for leaks.

Heavy draws of hot water with 

very cold refill water.

Let water heater warm up. Problem should go away.

If it persists, check all plumbing connections for leaks.

Water heater is undersized.

Install size of water heater that meets demand.

Combustion odours.

Insufficient secondary air.

Provide fresh air ventilation.

Heater installed in a confined area.

Provide fresh air ventilation.

Flue clogged.

Clean. Check for source of trouble and correct.

Smoking and carbon

Insufficient secondary air.

Provide fresh air ventilation.

Low gas pressure.

Check with gas utility company.

Burner flame yellow, lazy.

Refer to The burner flame is yellow and lazy.

Flue clogged.

Clean. Check for source of trouble and correct.

Defective gas control valve.

Replace with new gas control valve.

Heater installed in a confined area.

Provide fresh air ventilation.

The pilot flame is too small.

Low gas pressure.

Check with utility.

Pilot line or orifice clogged.

Clean. Check for source of trouble and correct.

Smelly water.

High sulfate or mineral content in water.

Change magnesium anode to an aluminum anode

and bleach tank.

Summary of Contents for GE-IM016En-0312

Page 1: ...sing property damage personal injury or death DO NOT store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS DO NOT try...

Page 2: ...f an FVIR technology equipped water heater due to a flammable vapour shutdown is not covered under the terms of the Standard Basic Limited Warranty Safety Information 3 Installation Instructions 4 Loc...

Page 3: ...tial hazards that can kill or hurt you and others All safety messages will follow the safety alert symbol and either the word DANGER or WARNING Serious injury or death can occur if you do not follow t...

Page 4: ...hteen 18 inches 45 7 cm from the top see Figure 1 Combustion and Ventilation Air Supply In order for the water heater to operate properly it must be supplied with an uninterrupted flow of clean com bu...

Page 5: ...eans of a duct This duct shall be sized accord ing to CAN CSA B149 1 and terminate within 1 foot above and within 2 feet horizontally from the burn er level of the appliance having the largest input I...

Page 6: ...eing highly flam mable become highly corrosive acid compounds when burned Exposure to such compounds can be hazardous and lead to premature product failure Should the water heater fail due to exposure...

Page 7: ...not exceed 75 of the vertical vent height in no case exceeding 20 feet 6 1 m All horizontal runs must have a minimum rise of 1 4 inch per foot 21 mm m of run See Figure 8 All joints must be securely...

Page 8: ...nts of the new water heater This new relief valve must meet all local codes or at a minimum the require ments listed above Never install any other type of valve between the relief valve and the water...

Page 9: ...tional Fuel Gas Code ANSI Z223 1 in the United States Only new piping with cleanly cut threads may be used together with a suitable sealing compound that is approved for natural and propane gases It i...

Page 10: ...an the potable water heating system 5 Where water temperature in excess of 140o F 60o C is required for a space heating application a mixing valve must be installed in the potable side of the system T...

Page 11: ...manufacturer s supplied drafthood been installed correctly L Is the vent piping made of an approved material and sized correctly L Has the venting been installed with 1 4 inch rise per foot 21 mm m of...

Page 12: ...light any appliance DO NOT touch any electric switch DO NOT use any phone in your building From a neighbour s phone immediately call your gas supplier Follow the gas supplier s instructions 1 STOP Rea...

Page 13: ...decrease the temperature or coun terclockwise to increase the temperature The reference mark on the temperature dial indicated by a large triangle represents 130 F 54 C see Figure 9 Each mark to the...

Page 14: ...ass to examine the flames A soft blue flame indicates proper gas combustion A yellow tipped flame indicates poor combustion With a vacuum cleaner remove any dust lint and dirt accumulation on or aroun...

Page 15: ...ve 5 Connect one end of a garden hose to the water heater drain valve and put the other next to a free flowing drain 6 Open the drain valve by inserting a flat head screwdriver into the slot on the he...

Page 16: ...rain valve 7 Overflow tube 8 Baffle 9 Flue reducer 10 Drafthood 11 Anode 12 Dip tube 13 Temperature pressure relief valve 1 Burner 2 Inner door Part 1 3 Outer access door 4 Resettable thermal switch 5...

Page 17: ...ve The flame burns at the orifice Low gas pressure Check with gas utility company Defective gas control valve Replace with new gas control valve The pilot will not light or remain lit No gas Check wit...

Page 18: ...ater drips from the relief valve Heater stacking Lower gas control valve setting Excessive water pressure Install a pressure reducing valve Thermal expansion in a closed water system Install an expans...

Page 19: ...age caused by not having the water heater installed adjacent to a free flowing drain in the event of water leakage 10 If the heater is operated at water temperatures exceeding the maximum setting of t...

Page 20: ...___________________________________________________________ ________________________________________________________________________________ ___________________________________________________________...

Reviews: