OptiFeed 4.0 (PP07)
Fault clearance
•
67
Incident
Causes
Corrective action
Power pack is defective (PP07-
S)
Replace
Fuse is defective (PP07-S)
Replace
Main switch is defective (PP07-
S)
Replace
Indicator
flashes
The parameter memory test
was erroneous
Reset to the default values:
Press for 5 seconds
Then set parameters, if necessary
Powder pump is not
conveying, indicator
is
not flashing
No
Pump on
control signal
A control signal must be applied at
connection
2.1
PIN 2
Powder pump is not
conveying, indicator
is
flashing
If the LEDs on the valve
connectors do not light up, the
pump control or corresponding
valve is defective
Replace pump control or send it in
for repair
Replace the defective valve