8257
23/32
10.1 Installation
CAUTION
Damage to the solenoid coil or bush!
®
If the solenoid coil is used as a lever,
the solenoid coil and bush could be
destroyed.
G
Use only the spanner
fl
ats provided to
screw the solenoid valve to the piping.
CAUTION
Damage to the valve body!
G
The solenoid valve may only be
installed in aligned pipes in order to
avoid stresses in the valve body.
Installing the solenoid valve
G
Clean the piping system before installing
the valve.
G
If necessary,
fi
t a strainer in front of the
valve inlet.
G
Remove the protection caps from the
valve inlet and valve outlet.
G
Screw the solenoid valve onto the piping
in accordance with the
fl
ow direction and
seal with appropriate sealant.
G
Use the spanner
fl
ats to screw the valve
in position.
10.2 Electrical connection
DANGER
Danger from electric shock!
®
There is a danger of injury or
death (if operating voltage
is higher than safe extra low
voltage)!
G
Electrical connection only to
be carried out by an electrical
expert.
G
Disconnect the cable from the
power supply before making
the electrical connection.
Inserting the cable
Inserting the cable
G
Remove the cable gland
1
and
fi
screw
5
.
G
Insert the cable through the cable gland
1
,
washer
2
, rubber sleeve
3
and the plug
housing
4
.
G
Connect the cable.
Summary of Contents for 8257
Page 15: ...8257 15 32...
Page 29: ...8257 29 32...
Page 30: ...8257 30 32...
Page 31: ...8257 31 32...