85198A_Manual of Electrical Installation for Pressure Probes KH-SIL2-Mobyle-series_07-2019_ENG

1. General Precautions

The system must be used only in accordance with the required protection level.

The sensor must be protected against accidental knocks and used in accordance with the instrument’s ambient characteristics and per-

formance levels.

Sensors must be powered with non distributed networks.

For outdoor installations or with cables longer than 30 m*, proceed as indicated at paragraph 3.

(*) See further limitations for Safety applications at paragraph 5.

2. Transmitters with amplified analog output

Transducers: KH SIL2 series

Outputs: 0.5...10.5V; 0.5...5.5V; 0.1...10.1V; 0.1...10V; 1...5V; 1...6V; 1...10V; 0.2...10.2; 0.5 … 4.5V ratiometric; 4...20mA, etc...

Installation remarks

- The transducer must be grounded (normally through the machine body or equipment it is installed on).

- Use a shielded cable only. The cable shield must be grounded on PLC side and left floating on machine side (on KH version with M12

  electrical connector it’s possible to connect the shield on machine side by leaving floating the PLC side).

- To prevent interference, separate the power cables from the signal cables.

Machine

Press

Equipment

Transducer

Ground

Cable shield floating

PLC / Instrument

Pressure port

Cable connector

Cable shield to ground

Shielded cable

Standard installation (recommended)

Summary of Contents for KH-SIL2 Series

Page 1: ...ns pag 2 2 Transmitters with amplified analog output pag 2 Standard installation pag 2 Electrical connections series KH pag 3 3 Protection for outdoor installations of analog sensors pag 4 4 Technical specifications pag 5 5 Safety content according to IEC EN 62061 paragraph 7 pag 6 This manual is related to KH Series pressure transducer SIL2 certified according to the standards IEC EN62061 GEFRAN ...

Page 2: ...ers with amplified analog output Transducers KH SIL2 series Outputs 0 5 10 5V 0 5 5 5V 0 1 10 1V 0 1 10V 1 5V 1 6V 1 10V 0 2 10 2 0 5 4 5V ratiometric 4 20mA etc Installation remarks The transducer must be grounded normally through the machine body or equipment it is installed on Use a shielded cable only The cable shield must be grounded on PLC side and left floating on machine side on KH version...

Page 3: ...nsor is connected in series with the current loop Interfaces with SRP CS and voltage devices RATIOMETRIC AND VOLTAGE AMPLIFIED OUTPUT CURRENT AMPLIFIED OUTPUT mod E Red Black Red Black White OUTPUT POWER SUPPLY SIGNAL POWER SUPPLY 2 1 3 4 G Deutsch DT04 4P Z M12 x 1 4 pin S AMP Superseal 1 5 E EN 175301 803 K Metri Pack 150 Protection IP67 Protection IP67 Protection IP67 Protection IP67 Protection...

Page 4: ...ND PLC side Ground D4 D1 D2 D3 J2 J2 J2 Transducer side 24Vdc Transducer side OUT Transducer side GND B72210 S 250 K01 B72210 S 250 K01 B72210 S 250 K01 B72210 S 250 K01 PLC ground machine ground 1 1 1 1 1 1 1 Pressure Analog current output CAL signals if any do not require protection J1 J1 J1 PLC side 24Vdc PLC side IN PLC side Ground D1 D3 J2 J2 Transducer side 24Vdc Transducer side OUT B72210 S...

Page 5: ...rature effects over compensated range zero 0 01 FS C typ 0 02 FS C max Temperature effects over compensated range span 0 01 FS C typ 0 02 FS C max Response time 10 90 FSO 1 msec Warm up time 3 30 sec Mounting position effects Negligible Humidity Fino a 100 RH non condensing Weight 80 120 gr nominal Mechanical shock 100g 11msec according to IEC 60068 2 27 Vibrations 20g max at 10 2000 Hz according ...

Page 6: ...urpose to verify that there are no occlusion of the pressure channel which would lead to malfunctioning The inspection is visual after removing the probe from the process seat Frequency every year Testing the sensor calibration The test is intended to check the correctness of the transduction curve of the sensor It s done by applying known pressure points to the transducer and checking the output ...

Page 7: ...ector broken Sensor not connected Sensor not powered Bridge broken 1 Power down and remove the sensor 2 Check that the power supply is connected If necessary restore the power supply 3 Check for continuity between the pins of the connector and the power supply If necessary replace the cable and the connector 4 Check if the power values are within the specifications indicated in this manual If nece...

Page 8: ...8 85198A_Manual of Electrical Installation for Pressure Probes KH SIL2 Mobyle series_07 2019_ENG via Sebina 74 25050 PROVAGLIO D ISEO BS ITALIA tel 0309888 1 fax 0309839063 Internet http www gefran com ...

Reviews: