Triac output
(option, only for 96 format)
20...240Vac ±10%, 3A max
Snubberless, inductive and resistive load I
2
t = 128A
2
S
Logic output
Main input
2Vac, 20Vac, 200Vac, 500Vac, Ri ≥ 1MΩ
Max. continuous voltage = 600Vac
Max. voltage for 1 minute = 900Vac
Voltage pulse 1,2/50ms = 2Kvpeak
20mAac, 50mAac, 200mAac, Ri = 1,6Ω
Max. continuous current = 400mAac at 50°C
1Aac, 5Aac, Ri = 16mΩ
Max. continuous current = 5.5Aac at 50°C
Max. frequency = 60Hz
For correct and safe
installation, follow the
instructions and observe
the warnings contained
in this manual.
1 • INSTALLATION
• Dimensions and cut-out: Panel mounting
Panel mounting:
Fix the device with the bracket provided before making any electrical connections.
To mount two or more devices side by side, use the cut-out dimensions shown above.
CE MARKING: EMC (electromagnetic compatibility): conforms to directive 2014/30/EU
with reference to standard EN61326-1
Safety LVD: conforms to directive 2014/35/EU with reference to standard EN 61010-1
MAINTENANCE: Repairs must be done out only by trained and specialized personnel.
Cut power to the device before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene, etc.).
Use of these solvents can reduce the mechanical reliability of the device.
Use a cloth dampened in ethyl alcohol or water to clean the external plastic case.
SERVICE: GEFRAN has a service department. The warranty excludes defects caused
by any use not conforming to these instructions.
2 • TECHNICAL SPECIFICATIONS
!
40A 48 / 40A 96
ALTERNATING CURRENT/VOLTAGE INDICATOR - INTERCEPTOR
SOFTWARE VERSION 1.0x / 2.0x
code 81661G / edition 10 - 09/2016
USER’S MANUAL
Faceplate protection
IP65
Working / Storage temperatures
0 to 50°C / -20 to 70°C
Relative humidity
20 to 85%, non-condensing
Installation
Panel mounting, extractable from front
Weight
160g (mod. 48); 320g (mod. 96) for the complete version
Resolution
>13bit - 8000 points
Linear scale ranges
-1999 to 9999 (with 4 digit display)
-999 to 999 (with 3 digit display - only for model 96)
Configurable decimal point position
Alarms (set points)
Maximum of three configurable alarms:
absolute, deviation, symmetrical deviation.
Adjustable hysteresis
Alarm masking
- exclude on power-up
- latch reset from key and/or external contact
- insert delay filter (DON, DBI, DOF, DPO)
- set minimum intervention time
Relay contact
NO (NC) 5A, 250V
11VDC, Rout = 220 Ω (6V/20mA)
Fault settings
Alarm states can be configured in probe fault
condition
Analog retransmission (option)
4 to 20mA, max. 150 Ω load
Logic input
Ri=5.6KΩ (24v, 4mA), 1500 V isolation
Logic input functions
configurable for alarm memory reset, hold, flash,
zero, selection of max., min. peak value, peak-peak
Fuse (inside device, not
operator serviceable)
100 to 240Vac/dc - type T - 500mA - 250V
11 to 27Vac/dc - type T - 1.25A - 250V
Power supply (switching)
40A 48 (standard) 100...240Vac ±10% - 8VA
(optional) 20...27Vac/dc ±10% - 8VA
40A 96 (standard) 100...240Vac/dc ±10% - 7,5VA
(optional) 11...27Vac/dc ±10% - 5VA
50/60Hz
Display
3, 4 digit red LED’s
mod. 48 digit height 10mm (4 digits)
mod. 96 digit height 20mm (3 digits),
digit height 14mm (4 digits)
Keys
3 mechanical keys (Raise, Lower, F)
Accuracy
0.2% f.s. for 2 Vac, 20 Vac, 20mAac inputs
50mAac, 1Aac, at room temperature of 25° C
0.5% f.s. for 200Vac, 500Vac, 200mAac, 5Aac
inputs, values shown are for max. rms value with
sine wave signal
Environmental conditions of use
for internal use only, altitude up to 2000m
1