GH10PA USER MANUAL

 

PAGE 

9

 

PPUH “GECO” Sp. z o.o. [Ltd.]                           Issue II 

SINCE DECEMBER 2011

 

6.2.

 

Automatic operation mode 

By pressing 

, you can enable the automatic operation mode – the Controller lights up the 

upper

 indicator 

on 

 (

 ). 

6.2.1.

 

Firing up 

This mode of operation is indicated by the blinking of the 

upper

 indicator on 

 (

 ). Firing up 

consists in controlling the burner feeder, the fan and the ignition heater so as to switch to the Automatic 
Operation Mode (if 

F34=0

, then the ignition heater cycle is skipped – Controller without ignition heater 

support) without the need to enable it manually. 

The fan operates continuously providing the output indicated in the 

F36

 service setting and the 

Controller additionally indicates whether it activates the feeder, the fan or the heater.  

The heater activation and operation are indicated by means of a 

horizontal

 line on the left side of the 

display, in the 

lower

 sign segment, on the Controller main display screen 

(

 

section 1.3 page 4

)

If the sensor detects fire during firing up (sensitivity drops below the value indicated in the 

F39 service 

setting

), the firing up process is terminated and the Controller switches to automatic operation. The firing up 

process follows the scheme below: 

 

Fuel container 

Fan 

 

Heater 

Fan 

F35 

FUEL 

 FEEDING 

FIRING UP 

PHASE 1 

F34 

FIRING UP 

MODE 2 

F37 

AUTOMATIC 

MODE 

NO 

Flame detection?  

 

-Cycle 1  

-Cycle 2  

-Cycle 3  

LEGEND: 

NO 

YES

 

Flame detection ?  

AUTOMATIC 

MODE 

YES

 

AUTOMATIC 

MODE 

Flame detection?  

NO 

TAK

 

YES

 

Fan 

GOING OUT 

ALARM 14

 

 

Fig. 2. Diagram showing firing up process.  

Summary of Contents for GH10PA

Page 1: ...applicable Instructions before connecting and starting up any of our products Should any doubts arise please contact our Company between 8 a m and 4 p m Attention At the bottom of each page you will...

Page 2: ...IGURATION 8 6 2 AUTOMATIC OPERATION MODE 9 6 3 MANUAL OPERATION MODE 11 6 4 VIEWING TEMPERATURES 11 6 5 ALARMS 12 6 6 POWER FAILURE 12 6 7 BOILER BURNOUT DETECTION 12 6 8 MAXIMUM FEEDER TEMPERATURE DE...

Page 3: ...ry in described instructions to follow the sequence of carried out operations The unit may be damaged or destroyed in case of any error or proceeding in discord with the description Important This sym...

Page 4: ...Mount Technology SMT It is designed to control the main Central Heating CH water circuit Control parameters can be adjusted to the current operating conditions and boiler type The Controller includes...

Page 5: ...5 86 Fan 1A 200W 90 202 37 Heater 3A 600W 100 149 16 4 ELECTRICAL SYSTEM AND CONNECTION RULES Boiler room should be equipped with 230V 50Hz electrical system according to applicable regulations Electr...

Page 6: ...I SINCE DECEMBER 2011 5 QUICK START Carry out the following operations in order to activate the GH10PA controller quickly 1 Connect the unit to the mains plug in power supply cable Switch on the contr...

Page 7: ...g screen will appear and the controller will start automatic operation based on preset factory parameters Table 1 Factory settings chart User parameter Description Factory settings U0 Boiler preset te...

Page 8: ...INCE DECEMBER 2011 6 OPERATION OF THE GH10PA 6 1 System configuration Fig 1 Central Heating circuit INPUT OUTPUT T1 Boiler temperature P1 Burner feeder T2 Feeder temperature P2 Fan C1 Flame sensor P3...

Page 9: ...e Controller additionally indicates whether it activates the feeder the fan or the heater The heater activation and operation are indicated by means of a horizontal line on the left side of the displa...

Page 10: ...e 4 6 2 4 CH pump In the AUTO mode the CH pump is activated when the temperature of the boiler water is higher or equal to the value set in the F06 service setting factory setting is 40 C The CH pump...

Page 11: ...tivation and operation are indicated by means of a horizontal line on the left side of the display in the lower sign segment on the Controller main display screen section 1 3 page 4 6 4 Viewing temper...

Page 12: ...the display shows time in seconds remaining until the end of the period together with indication of its condition before the power outage blinking A for AUTO mode blinking P for MAINTAIN mode blinking...

Page 13: ...er activates for the period of time set in the F16 service setting to eject the ignited fuel from the feeder During the F16 period the fan remains inactive When the time set in F15 service setting ela...

Page 14: ...o to U1 Set the new desired value Save the new temperature setting Move to the U2 setting 7 3 Feeder stop time U2 This is the period of time between two consecutive fuel feeds in the AUTO mode Setting...

Page 15: ...ALS 15 AND 16 SHOULD BE SHORTED If due to boiler temperature rise the temperature limiter is activated and opens its terminals it will disable feeder and fan power supply in order to stop fuel and air...

Page 16: ...P1 54 55 Flame sensor C1 09 N Burner feeder P1 55 56 57 Fuel level sensor C2 06 L CH pump P4 05 N CH pump P4 08 L Container feeder P5 07 N Container feeder P5 04 L Heater P3 03 N Heater P3 02 N Power...

Page 17: ...the need for selective collection of worn out electrical and electronic equipment It means that this product should not be disposed of with other household wastes Proper disposal of aged and worn out...

Page 18: ...ANUAL PAGE 18 PPUH GECO Sp z o o Ltd Issue II SINCE DECEMBER 2011 P P U H Geco Sp z o o Ltd Cholerzyn 376 32 060 Liszki Poland ph 48 12 636 98 11 636 12 90 fax 48 12 636 20 02 http www geco pl e mail...

Reviews: