Page 13 Edition I
03.12.2012
- Signals that the anti-legionella function is active.
This function is available only in the second heating configuration.
The anti-legionella function takes priority over all others, meaning that it is performed by
the controller first. When this function is enabled, the temperature of the water in the boiler is
raised to 70°C and this temperature is maintained for ten minutes.
The controller reports an anti-legionella function error if, within 240 minutes of the
function being activated, the temperature in the hot water tank does not reach 70 ° C. The
following error message appears on the display.
- Signals anti-legionella function error
Activating the anti-legionella function raises the water temperature to
70 ° C. Use hot water with extreme caution, as this may result in
scalding.