Soft starter failure notification
Failure in soft starter shows as Soft starter E25 failure notifica-
tion on controller's display. The amount of flashes of the red
LED light on soft starter indicates the failure.
Number of
flashes, red
LED
Failure
Operation
2
Incorrect
phase se-
quence
Changing the phase se-
quence
3
Incorrect volt-
age
Automatic restart 5 min
after the failure
4
Incorrect fre-
quency
Automatic restart 5 min
after the failure
5
Rotor is not
spinning
Automatic restart 5 min
after the failure
6
Start time > 1
s
Automatic restart 5 min
after the failure
7
Overheating
Automatic restart 5 min
after the failure
8
Over current
after start-up
Automatic restart 5 min
after the failure
9
Asymmetrical
input voltage
Automatic restart 5 min
after the failure, if all
phases are connected