26
Gebwell GEMINI
9.5
Cleaning the collector filter
Check filter E by first closing valves A and B, and opening the
filter’s cover. After cleaning the filter, open valve A first, in
which case air exits the filter’s nest to the expansion vessel F.
Open valve B.
10
ACTIVATING THE HEAT
PUMP
Upon delivery, all the pump’s motor protection switches and
circuit breakers are in the
0
position.
When commissioning, the controller’s settings must be ac-
cessed at
Expert
level.
Commissioner’s menu:
10.1
Before activation
Before activating the heat pump, ensure that
the collector has been filled with heat transfer liquid
the collector has been vented carefully
the collector’s filter has been cleaned after venting
all the collector’s valves have been opened
the programming of external source pump has been
carried out
the heating system has been filled with water
the heating system has been vented
the heating system’s water temperature should be
<20°C
the domestic hot water system must be filled
the outdoor sensor has been connected
the heating sensors have been connected
the electrical connections are correct
the compressor’s motor protection switch (F1) is in
the OFF position
electricity is lead to source pump
the source pump’s line protection switch F4 is in OFF
position.
10.2
Activation
1.
Set the heat pump’s main switch to (Q1) position I.
Summary of Contents for GEMINI 40
Page 1: ...Installation Operation and Maintenance Manual GEMINI Heat Pump WWW GEBWELL FI...
Page 57: ...v1 6 29082018 57 20 ENERGY LABELS...
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......