
12.3.5 Four weeks before restarting
•
Check the moisture content and ageing condition of the refrigerating machine
oil. Analyse the oil for this purpose. Compare the results of the analysis with
the values for fresh oil. We recommend an oil change after 1 year at the lat-
est. (See maintenance instructions.)
•
Check the insulation resistance of the drive motors (see the operating manual
for the electric motor).
•
Run the oil pump (if present) for about 5 minutes.
•
Check the system for leak tightness.
Decommissioning
Temporary decommissioning
L_151511_2
110
19.12.2019
Summary of Contents for RedGenium
Page 6: ...L_151511_2 6 19 12 2019 ...
Page 8: ...L_151511_2 8 19 12 2019 ...
Page 14: ...L_151511_2 14 19 12 2019 ...
Page 118: ......