Fault table
Fault
Cause
Remedy
Malfunction of compressor suction valve,
pressure valve or overflow safety valve.
Repair.
(see installation and maintenance instruc-
tions for compressor).
Compressor output controller does not
work.
Repair.
(see installation and maintenance instruc-
tions for compressor).
Discharge pressure and/or discharge tem-
perature too high.
Condenser output too low due to contami-
nation.
Clean.
Condenser output too low as cooling
medium flow (heat carrier flow) is too low.
Increase cooling medium flow (heat carrier
flow).
Cooling medium temperature (heat carrier
temperature) too high.
Lower cooling medium temperature (heat
carrier inlet temperature).
Overfilling with refrigerant
Drain refrigerant.
There is air or other non-condensible
gases in the refrigerant circuit.
Vent the refrigerant circuit.
Stop valve in the pressure pipe not fully
open.
Open stop valve completely.
Leakage in safety valve or compressor
pressure valve.
Repair.
The overpressure switch or discharge
pressure sensor is defective or the switch-
off value is set wrongly.
Adjust overpressure switch/discharge
pressure sensor correctly or replace.
Oil pressure too low.
Oil quantity in compressor crankcase too
low.
Add oil and/or check oil return system.
Oil filter on suction and/or pressure side is
clogged.
Clean or replace
(see installation and maintenance instruc-
tions for compressor).
Incorrect setting or defective lubricating oil
pressure regulator.
Adjust or repair
(see installation and maintenance instruc-
tions for compressor).
Refrigerant in the oil,
Defective compressor crankcase oil
heater.
Refrigerant circuit overfilled – drain refrig-
erant.
Rapid pressure loss in crankcase at start-
ing.
Check if refrigerant supply to evaporator is
blocked. check injection valve.
Excessive oil temperature.
Room temperature too high.
Improve ventilation.
With existing oil cooler: insufficient cooling
capacity.
Check the function of the air-cooled oil
cooler
(fan in operation, air passage not obstruc-
ted).
Oil temperature too low.
Crankcase heating not working properly.
Check the crankcase heater.
Refrigerant in the oil,
Refrigerant circuit overfilled – drain refrig-
erant.
Maximum motor current.
Limit value set to less than 105% of full
charge current.
Correct limit value.
Compressor drive motor malfunction.
Consult the manufacturer.
Voltage too low.
Check voltage.
Refrigerant temperature too low.
Refrigerant temperature setpoint too close
to lowest temperature limit.
Correct setpoint.
Alarms
Instructions regarding malfunctions, their causes and remedies
L_151511_2
106