4.5
DIAGRAMSGRAMS CAPACITY CONTROL
Solenoid valve/cylinder numbering for electric capacity control
Compressor type
Solenoid
UNL
NO
No. 1
NC
No. 2
NC
No. 3
NC
No. 4
NC
Cylinder number / solenoid valves
V 700HS
1
2
3
4
-
V 1100HS
(3+4)
2
(5+6)
1
-
V 1400HS
(5+6)
7
8
(2+4)
(1+3)
V 1800HS
(5+7+8)
(9+10)
(1+2)
(3+4)
6
Capacity control steps
Compressor
type
Capacity %
16
Cylinders
Solenoids
V 700HS
25
1
-
50
1 + 2
1
75
1 + 2 + 3
1 + 2
100
1 + 2 + 3 + 4
1 + 2 + 3
V 1100HS
33
(3+4)
-
50
(3+4) + 2
1
67
(3+4) + (5+6)
2
83
(3+4) + (5+6) + 1
2 + 3
100
(3+4) +2 + (5+6) + 1
1 + 2 + 3
V 1400HS
25
(5+6)
-
37
(5+6) + 8
2
50
(5+6) + 8 + 7
1 + 2
62
(5+6) + 8 + (1+3)
2 + 4
75
(5+6) + (2+4) + (1+3)
3 + 4
87
(5+6) + 7 + (2+4) + (1+3)
1 + 3 + 4
100
(5+6) + 7 + 8 + (2+4) +
(1+3)
1 + 2 + 3 + 4
V 1800HS
30
(5+7+8)
-
40
(5+7+8) + 6
4
50
(5+7+8) + (9+10)
1
60
(5+7+8) + (9+10) + 6
1 + 4
70
(5+7+8) +(9+10) + (1+2)
1 + 2
80
(5+7+8) + 6 + (3+4) +
(1+2)
2 + 3 + 4
16
Refer to the swept volume expressed as a percentage of the full-load swept volume
APPENDIX; Product Information (PI)
DIAGRAMSGRAMS CAPACITY CONTROL
P-NL-094_imm_VHS_English_13
54