with only one HP cylinder in operation and that the minimum LP/HP swept
volume ratio for any part-load step is ϕ = 2.
Therefore, for all Grasso two-stage types a fast pull- down electric capacity
control system has been developed, which allows the compressors to be started
with two or more HP cylinders in operation and which includes one or more part-
load steps with volume ratio ϕ = 1.
4.4
DIAGRAMS SINGLE STAGE AND BOOSTER
Solenoid valve/cylinder numbering for electric capacity control
Compressor
type
Solenoid
UNL
NO
No. 1
NC
No. 2
NC
No. 3
NC
No. 4
NC
Cylinder number / solenoid valves
300 &
700
1
2
3
4
-
450 &
1100
(3+4)
2
(5+6)
1
-
600 &
1400
(5+6)
7
8
(2+4)
(1+3)
1800
Before Sept. 2014
(7+8)
5
6
(9+10)
(1+2+3+4)
1800
From Sept.
2014
(5+7+8)
(9+10)
(1+2)
(3+4)
6
Capacity control steps
Compressor
type
Capacity %
20
Cylinders
Solenoids
V 300
&
V 700
25
1
-
50
1 + 2
1
75
1 + 2 + 3
1 + 2
100
1 + 2 + 3 + 4
1 + 2 + 3
V 450
&
V 1100
33
(3+4)
-
50
(3+4) + 2
1
67
(3+4) + (5+6)
2
83
(3+4) + (5+6) + 1
2 + 3
100
(3+4) +2 + (5+6) + 1
1 + 2 + 3
V 600
&
V 1400
25
(5+6)
-
37
(5+6) + 8
2
50
(5+6) + 8 + 7
1 + 2
62
(5+6) + 8 + (1+3)
2 + 4
75
(5+6) + (2+4) + (1+3)
3 + 4
20
Refer to the swept volume expressed as a percentage of the full-load swept volume
APPENDIX; Product Information (PI)