PRODUCT INFORMATION
LIQUID CHILLER GRASSO DX R
200 ... 1600
30
_601011_pi_dxr_gbr_1_.doc
DX chiller type RR 600
Secondary refrigerant outlet temperature at evaporator (°C)
Refrigerating capacity in kW
Driving capacity in kW
10 6 2 0 -2 -6 -10
32
715
140
615
136
525
134
484
132
445
130
376
126
315
123
38
688
162
591
156
503
151
464
149
426
147
359
144
300
141
Cooling medium
outlet temperature
at condenser (°C)
45
669
179
574
169
488
164
450
162
413
161
348
158
290
154
DX chiller type RR 800
Secondary refrigerant outlet temperature at evaporator (°C)
Refrigerating capacity in kW
Driving capacity in kW
10 6 2 0 -2 -6 -10
32
923
180
798
177
681
173
630
170
581
167
493
163
415
159
38
890
208
768
201
659
195
608
192
561
190
475
185
400
182
Cooling medium
outlet temperature
at condenser (°C)
45
875
225
754
218
643
212
594
209
548
207
463
203
389
196
DX chiller type RR 750
Secondary refrigerant outlet temperature at evaporator (°C)
Refrigerating capacity in kW
Driving capacity in kW
10 6 2 0 -2 -6 -10
32
878
167
748
161
654
159
606
157
560
154
476
149
401
145
38
854
194
739
186
635
180
588
177
543
174
461
170
388
165
Cooling medium
outlet temperature
at condenser (°C)
45
838
209
724
201
622
195
576
192
532
190
451
185
380
178
Summary of Contents for Grasso DX 600