 Commissioning

11. This setting depends on the application.
  Setting ex factory: Internal control

12.  Setting at Internal control:  

Pressure Transmitter [bar]

13. The sensor range is to be adjusted later.
 

13.1  Sensor signal 4-20 mA.

14.  This connection is already pre-wired  

by GEA.

15. Check switch position below the user interface.

Compressor

Attention!

Connect your 

4-20-mA-Signal  

as shown:

+ 13
 - 54

Compressor

Attention!

Please switch 

A54 to

position I

(under LCP)

U   I

Select Sensor Range:

-1 / +12 bar

Compressor

Select Sensor Signal

4-20 mA

Sensor Type:

Pressure Transmitter 

[

bar

]

Compressor

Select internal or external 

control

Internai control

Compressor

Summary of Contents for Bock Plusbox Series

Page 1: ...ssembly instructions 96284 09 2016 Gb Translation of the original instructions SHG X 34e 215 4 S PB SHG X 34e 215 4 S P P SHG X 34e 255 4 S PB SHG X 34e 255 4 S P P SHG X 34e 315 4 S PB SHG X 34e 315 4 S P P SHG X 34e 380 4 S PB SHG X 34e 380 4 S P P ...

Page 2: ...rve the safety instructions contained in these instructions and in the compressor instructions These instructions must be passed onto the end customer along with the unit in which the Plusbox is installed Observe also the other documentation included with the Plusbox GEA Bock GmbH 72636 Frickenhausen GEA Bock GmbH Benzstraße 7 72636 Frickenhausen Germany Telephone 49 7022 9454 0 Fax 49 7022 9454 1...

Page 3: ...24 6 1 Status Messages 6 2 Application Example 7 Maintenance 26 7 1 Preparation 7 2 Work to be carried out 8 Technical data 27 9 Dimensions and connections 28 10 Service 29 Note According to Commission Regulation EU 2015 1095 of 5 May 2015 implementing Directive 2009 125 EC of the European Parliament and of the Council with regard to ecodesign requirements for professional condensing units startin...

Page 4: ...comparable training which enablespersonneltoassemble install maintainandrepairrefrigeration and air conditioning systems Personnel must be capable of assessing the work to be carried out and recognising any potential dangers DANGER Indicates a dangerous situation which if not avoided will cause immediate fatal or serious injury WARNING Indicates a dangerous situation which if not avoided may cause...

Page 5: ...urns and skin damage WARNING The Plusbox may not be used in potentially explosive environments These assembly instructions describe the standard version of the Plusbox named in the title manufac tured by GEA The Plusbox is intended for installation in a machine within the EU according to the EU Directives 2006 42 EC Machinery Directive 2014 68 EU Pressure Equipment Directive Commissioning is permi...

Page 6: ...cation of its contents to others without express authorization is M Luftgekühlter Verflüssigungssatz Air cooled condensing unit Aggregat Bezeichnung unit description Bestehend aus composed of Verdichter Teile Nr compressor part no X Verdichter Teile Nr X compressor part no Sammler Teile Nr receiver part no Inhalt Ltr volume Ltr SHG X 34e 215 4 PB 16050 16058 60028 8 SHG X 34e 215 4 SPB 16054 16062...

Page 7: ...HGX34e 315 4 P P AV38125A001 SHG 4 3 e 380 PB 4 S X 2 3 Type key example HG Hermetic Gas Cooled suction gas cooled X Ester oil charge 3 S Stronger motor 4 PB Plusbox P P Plug and Play Plusbox 4 Motor variant 3 Number of poles Swept volume e Series Number of cylinders Size Oil charge Series GEA Bock GmbH 72636 Frickenhausen Germany 19 28 2 Product description 2 2 Name plate example Fig 3 ...

Page 8: ...ty damp atmosphere or a combustible environment F E D C 1 2 3 INFO New compressors are factory filled with inert gas 3 bar nitrogen Leave this service charge in the compressor for as long as possible and prevent the ingress of air On the Plusbox backside there is a sheet metal in the area of the connection lines The sheet metal can be moved after releasing the four screws so the lines can be easie...

Page 9: ...et X3 Terminal strip terminal box Legend circuit diagram for Plusbox with accessories DANGER Risk of electric shock High voltage Only carry out work when the electrical system is discon nected from the power supply 4 Electrical connection to 4 2 Circuit diagram for Plusbox with frequency converter see Fig 10 ATTENTION For frequency converter operation Max permissible ambient temperature 10 C to 40...

Page 10: ...1 L1 T2 L2 T3 L3 QA1 EB1 PE EC1 3 M Θ BT2 Θ 21 22 FC1 13 14 1 L1 2 T1 3 L2 4 T2 5 L3 6 T3 FC1 I I I 21 22 QA2 X1 1 2 4 5 6 7 10 11 12 13 8 3 X3 1 2 PE 9 1 2 FC2 L N B1 B2 12 14 11 OG OG X3 11 1 2 QA2 3 4 5 6 PE PE 400V 4x4mm W1 1 2 3 PE 230 3x1 0mm W8 1 2 PE 230V 5x1 0mm W2 1 2 3 4 PE BT2 Θ X3 10 X3 9 L1 L2 L3 N PE Compressor terminal box ...

Page 11: ...bF HP LP ex factory not connected 5 6 7 8 9 P Oil BP2 BP1 13 14 BT3 A1 A2 QA2 14 15 18 17 19 20 21 16 22 23 24 PE Duopress P T2 N L M S 1 2 3 4 PE PE 13 14 QA2 230V 5x1 0mm W3 1 2 4 3 PE 230V 5x1 0mm W4 1 2 3 4 PE StSP1 StSP1 PE N ...

Page 12: ...1 0mm W6 230V 3x1 0mm W7 13 14 Freigabe Leistungsregler X1 PE 25 26 27 28 PE 29 30 1 X4 1 2 3 X5 1 2 3 1 2 PE PE 2 PE StSP1 N PE StSP2 4 1 Circuit diagram for Plusbox with accessories continuation Release Capacity regulator Capacity regulator rotation speed control fan ex factory not connected Fig 9 ...

Page 13: ...D GB F E 13 96284 09 2016 DGbF N PE 1 2 PE MA1 Kondensator lüfter 1 M 0 230V 3x1 0mm W5 PE 1 2 31 32 PE 1 PE1 Gehäuseboden 1 PE2 Gehäusedeckel PE PE housing cover housing base fan ...

Page 14: ...3 L3 QA1 EB1 PE EC1 3 M Θ 91 96 92 97 93 98 95 99 12 18 19 54 BP3 1 2 Duopress P 11 14 QA2 21 22 FC1 13 14 L1 T1 L2 T2 L3 T3 FC1 I I I X1 1 2 4 5 6 7 10 11 12 13 14 15 8 3 400V 4x4 0mm W9 PE 1 2 3 0 400V 4x4 0mm W10 1 2 3 PE 230V 3x1 0mm W11 1 2 230V 5x1 0mm W12 4 3 2 1 X3 12 11 13 PE PE 24V DC 3x1 0mm W17 1 9 PE PE 10 PE 24V DC 5x1 0mm W16 1 2 3 2 1 2 3 4 L1 2 0 L2 2 0 L3 2 0 N 2 1 PE 2 1 Compres...

Page 15: ...T3 01 Relais1 03 02 T2 N L M S A1 A2 QA2 18 17 19 20 21 16 230V PE1 0mm W13 1 2 3 4 230V 3x1 0mm W14 2 1 230V 3x1 0mm W16 PE 1 2 22 23 24 25 26 PE PE 27 28 29 PE 230V 5x1 0mm W18 PE 04 Relais2 06 05 A1 A2 QA3 PE 1 2 3 PE 1 2 FC2 X4 1 2 3 12 11 14 QA3 N PE Drehzahl steuerung Lüfter Konden sator lüfter ...

Page 16: ...ing Set the fan speed controller according to the operating conditions of the plant Commissioning EFCe 5 1 Commissioning Plusbox without EFCe 5 2 Commissioning Plusbox with EFCe Note the enclosed Danfoss product manual The function and operation of the user interface are described there Here take a look what you need to set values and parameters specifically for the GEA Plusbox Due to software upd...

Page 17: ... compressor 5 Set the maximum continuous current and the nominal speed You can find the values on the nameplate of the compressor Please select language English AKD Wizard Select Application Compressor AKD Assistent Which motor type is connected to the drive Asynchron VLT Assistent Select Motor Voltage 400 V Compressor Select Motor Frequency 50 Hz Max Cont Current MCC 9 000 A Compressor Enter Nomi...

Page 18: ...nd 70 Hz 10 This setting depends on the application 9 Set the desired recycle time We recommend 3 minutes Does the application include a sine wave filter No Compressor Would you like to run AMA Recommended AS takes a few min PM takes a few sec Yes Compressor Min Frequency 30 0 Hz Compressor Max Frequency 60 0 Hz Recycle Time Start to Start 3 1 min Compressor Does the application include a bypass v...

Page 19: ... Sensor signal 4 20 mA 14 This connection is already pre wired by GEA 15 Check switch position below the user interface Compressor Attention Connect your 4 20 mA Signal as shown 13 54 Compressor Attention Please switch A54 to position I under LCP U I Select Sensor Range 1 12 bar Compressor Select Sensor Signal 4 20 mA Sensor Type Pressure Transmitter bar Compressor Select internal or external cont...

Page 20: ...16 Set setpoint unit depends on the application 16 1 Select type of refrigerant 17 Set setpoint type Recommended setting Constant 18 Enter setpoint depends on the application Select Setpoint Unit C Compressor Select Refrigerant Type R404a Select Setpoint Type Constant Compressor Setpoint 10 000 C Compressor Max Setpoint Limit 40 000 C Compressor Min Setpoint Limit 60 000 C Cut out Value 25 000 C C...

Page 21: ... Setting ex factory No 22 Compressor setup completed 23 Go to main menu Compressor Compressor Setup Completed Do you wish to configure Pack Control No Compressor You now have the following options Go to Main Menu Compressor 6 24 Terminal 54 Skal Low Ref Feedb Value 1 000 0 000 C Analog input 54 0 000 C 6 2 6 25 Terminal 54 Skal High Ref Feedb Value 19 000 0 000 C Analog input 54 0 000 C 6 2 12 000...

Page 22: ...ime has elapsed 3 minutes Suction pressure is high enough No other parameters were change If other parameters were changed we recom mend to reset the EFCe to factory settings Afterwards have a look at the Danfoss product manual Follow again the instructions of the startup wizard 1 90 Motor Thermal Protection Thermistor shutdown 54 2 Motor Temperatur 12 6 A 1 9 2 1 93 Thermistor connection 4 Digita...

Page 23: ...certain frequencies you have the option to skip them From the main menu Parameter 4 61 Bypass speed from Parameter 4 63 Bypass speed to 5 Commissioning 4 61 Bypass Speed from O Hz 0 0 Hz Speed Bypass 4 6 0 000 C 0 000 C 4 63 Bypass Speed to O Hz 0 0 Hz Speed Bypass 4 6 0 000 C 0 000 C ...

Page 24: ...ent limit W59 Imax reached Rotation speed of the compressor is not increased e g if suction pressure too high when compressor first commissioned 4 Auto Remote Standby No release by the inverter safety chain is not open Status 5 000 C 0 00 A 10 6 C Auto Remote Cut out 0 0Hz 3940kWh Status 5 000 C 9 25 A 6 554 C Auto Remote Run on ref 25 0Hz 3939kWh Status 5 000 C 9 33 A 6 387 C Auto Remote Speed hi...

Page 25: ... messages Display 0 2 1 0 1 2 2 6 3 3 22 28 Temp C 30 15 10 0 P P C P P Cut out LP switch Cut in LP switch Room temperatur Cut in HP switch Cut out HP switch Cut out VLT Cut in VLT and Min Setpoint Limit VLT Auto Remote Standby Setpoint Max Setpoint Limit VLT Auto Remote Run on ref Auto Remote Standby Auto Remote Standby Auto Remote Cut out ...

Page 26: ...ser fan and machine room and then remove again before subsequent start up Neither dirt nor moisture are allowed to penetrate the machine room We recommend using compressed air and a soft brush for cleaning Further maintenance work in accordance with the instructions for assembly on the compressor WARNING Before starting any work on the compressor Switch off the compressor and secure it to prevent ...

Page 27: ... 80 18 3 10 5 2 60 600 7895 8 0 1 2 1 1 8 47 201 SHG34e 255 4 P P 22 10 17 0 9 8 2 60 600 7895 8 0 1 2 1 1 8 47 195 SHG34e 255 4 S P P 22 10 21 1 12 2 2 60 600 7895 8 0 1 2 1 1 8 47 200 SHG34e 315 4 P P 27 30 21 1 12 2 2 60 600 7895 8 0 1 2 1 1 8 47 198 SHG34e 315 4 S P P 27 30 25 5 14 7 2 60 600 7020 10 0 5 8 1 3 8 47 207 SHG34e 380 4 P P 33 10 26 1 15 1 2 60 600 7020 10 0 5 8 1 3 8 47 203 SHG34e...

Page 28: ... Drawing no 3 2 Part No Maßstab 0 1 über above Freigabe Approved z y Allgemeintoleranzen General tolerances Drawing No bis up to x w u t s Kund DIN ISO 2768 mK Ra Rz Ersat Dimension Passung Clearance Baumustergeprüft Type examination K Auftrag C Task Projektleiter Project leader 120 400 0 5 0 5 6 GEA Bock GmbH Benzstraße 7 72636 Frickenhausen Germany www bock de Unbemaßte Radien Undimensioned radi...

Page 29: ...6 UNF SHG34e 380 4 S PB 35 13 8 16 5 8 1 2 NPTF 7 16 UNF 7 16 UNF 7 16 UNF SV Suction line shut off valve FLA Liquid outlet SI Connection safety valve Y1 Connection liquid side lockable Y2 Connection liquid side not lockable Y3 Schrader connection speed controller fan 1 Further compressor connections can be found in the assembly instructions of the compressor Dear customer GEA compressors are top ...

Page 30: ...usen Germany Phone 49 0 7022 9454 0 Fax 49 0 7022 9454 137 info gea com gea com GEA Group is a global engineering company with multi billion euro sales and operations in more than 50 countries Founded in 1881 the company is one of the largest providers of innovative equipment and process technology GEA Group is listed in the STOXX Europe 600 index ...

Reviews: