Commissioning
26. Set parameters 1-90 to [2] Thermistor
shutdown.
27. Set parameters 1-93 to [4] Digital input 19.
.
28. Set parameter 5-12 to [0] without function.
This completes the setting of the EFCe.
To start the compressor, press the button
Auto on
. The compressor starts if:
- Relais QA2 has attracted
- Delay time has elapsed (3 minutes)
- Suction pressure is high enough
- No other parameters were change.
If other parameters were changed, we recom-
mend to reset the EFCe to factory settings.
Afterwards have a look at the Danfoss product
manual. Follow again the instructions of the
startup wizard.
1-90 Motor Thermal
Protection
Thermistor shutdown.
54.2%
Motor Temperatur
12.6 A
1-9*
2
1-93 Thermistor connection
[4] Digital input 19
87.0%
Motor Temperatur
9.08 A
1-9*
([O] without)
5-12 Terminal 27
[0] without function
87.0%
Digital inputs
9.08 A
5-1*
([O] without)