background image

10

Receptacles/Sub-bases

 

 

RAK204U 

RAK204D15P 

RAK204D20P 

RAK204D30P 

RAK204E15 

RAK204E20 

RAK204E30

 

Voltage 

N/A 

0/08 

0/08 

0/08 

5

 

Amps 

N/A 

15 

15 

0

 

Receptacle 

N/A 

NEMA-0R 

NEMA-0R 

NEMA-0R 

NEMA7-15R 

NEMA7-0R 

NEMA7-0R

0/08 Volt sub-bases include appropriate power cord kit.

5 Volt units are to be direct connected. Cordset through enclosed chaseway into interior sub-base receptacle meets the NEC requirements.

Sub-bases

Tandem

 

0/08V 15 Amp
NEMA-15R

Perpendicular

0/08V 0 Amp
NEMA-0R

Large tandem 

0/08V 0 Amp
NEMA-0R

265V 15 Amp

NEMA7-15R

265V 20 Amp

NEMA7-0R;  
receptacle used 
On 5V sub-base 
GE070-

265V 30 Amp

NEMA7-0R;  
receptacle used 
On 5V sub-base 
GE07

Power connection kits are required on all Zoneline

®

 chassis (see chart below).

The correct kit for the installation is determined by the voltage and amperage of the electrical circuit and the means of connecting the unit to the 
building wiring. If the unit is to be plugged into a receptacle, a line cord kit would be used; if the unit is to be permanently connected, a permanent 
connection kit would be used. 5 volt cord set units must be installed in compliance with National Electrical Code

®

Power connection kits

Required on all models. 
See specification sheet 
for heater KW and branch 
circuit ampacity.

RAK15/0

0/08 volt line cord 

connection kit

RAK157/07/07

0/08 volt universal 

power supply kit

RAK5157/507/507

5 volt universal power 

supply kit

230/208 volt

Line cord connected units

LCDI Power Connection Kit

RAK3153

RAK3203

RAK3303

Heater KW

.55/.09

.5/.8

5.00/.09

Watts

,550/,090

,50/,80

5,000/,090

BTUH

8,00/7,100

11,700/9,00

17,000/1,900

Amps

11./10.

15./1.

./0.

Min. circuit amps

15

0

0

Recommended 

protective 

device

15 amp 

time delay 

fuse or breaker

0 amp 

time delay 

fuse or breaker

0 amp 

time delay 

fuse or breaker

265 volt Permanent connected units*  (Cord set)

RAK5172

RAK5202

RAK5302

.55

.5

5.0

,550

,50

5,000

8,00

11,700

17,000

10.

1.8

19.

15

0

0

15 amp  

time delay fuse

0 amp  

time delay fuse

0 amp  

time delay fuse

*To be used with sub-base

230/208 volt

Direct connection kit**

RAK4157

RAK4207

RAK4307

Heater KW

.55/.09

.5/.8

5.00/.09

Watts

,550/,090

,50/,80

5,000/,090

BTUH

8,00/7,100

11,700/9,00

17,000/1,900

Amps

11./10.

15./1.

./0.

Min. circuit amps

15

0

0

Recommended 

protective 

device

15 amp 

time delay 

fuse or breaker

0 amp 

time delay 

fuse or breaker

0 amp 

time delay 

fuse or breaker

**To be used with sub-base or connection to building wiring

265 volt Direct connection kit**  

RAK5157

RAK5207

RAK5307

.55

.5

5.0

,550

,50

5,000

8,00

11,700

17,000

10.

1.8

19.

15

0

0

15 amp  

time delay fuse

0 amp  

time delay fuse

0 amp  

time delay fuse

**To be used with sub-base or connection to building wiring

Summary of Contents for Zoneline Premium AZ58H09D

Page 1: ...GE Zoneline packaged terminal air conditioners ...

Page 2: ... ...

Page 3: ...nd apartments All Zoneline units feature the exclusive GE Superseal system which minimizes energy usage by reducing air infiltration The result is maximum operating efficiency and a more comfortable room All Zoneline units are also very quiet thanks to a lower sound level and lower sound transmission The newest innovation in Zoneline units is the Dry Air 25 Series Similar to our Deluxe 2900 Series...

Page 4: ...its are equipped with microcomputer touch controls This feature gives the user better control over the temperature with a touch pad and an LED readout Optional corrosion treatment Deluxe Zoneline units can be ordered with special treatment to reduce the effects of corrosive environments Special treatments are placed on the outdoor coil and other components to extend the life of the unit Remote ins...

Page 5: ...om the air than standard GE packaged terminal air conditioners The Dry Air 25 is perfect for high humidity climates Available on 7000 9000 and 12000 BTU models Upfront filters For ease of cleaning all Zoneline units have interchangeable removable upfront filters made of long lasting nylon mesh thus assuring high performance and long life Electronic temperature limiting Heating and cooling temperat...

Page 6: ...of cleaning Long lasting nylon mesh Central desk control compatibility Remote thermostat capability Smartfan Fan cycle operation based on heat cool selection Deluxe Dry Air 25 series cooling with resistance heat Includes all features of 2900 series plus Removes 25 more moisture from the air than standard GE packaged terminal air conditioners Cool and dry air in less time than standard Zoneline mod...

Page 7: ...e control Standard Standard Standard Standard Fan Only setting 2 speed Hi Low Hi Low Hi Low Hi Low Indoor fan speed Hi Low Hi Low Hi Low Hi Low Cool heat only settings Hi Low Auto Hi Low Auto Hi Low Auto Hi Low Auto Staged heating 3 stage 3 stage Freeze Sentinel Standard Standard Standard Standard Heat Sentinel Standard Standard Standard Standard Temperature limiting Electronic 7 step Electronic 7...

Page 8: ...eating of rooms Smartfan fan cycle selection Select fan cycle or fan continuous independently for heating and cooling Solid state thermostat control Provides better room temperature control vs electromechanical temperature control device Freeze Sentinel Provides automatic protection against freezing by switching the unit to heat should the temperature of an unoccupied room drop to 41 F Heat Sentin...

Page 9: ...mperature control device Freeze Sentinel Provides automatic protection against freezing by switching the unit to heat should the temperature of an unoccupied room drop to 41 F Heat Sentinel Provides automatic protection against overheating by switching on the unit to cool should the temperature of an unoccupied room reach 85 F Room occupancy sensor compatible Ready for connection to room occupancy...

Page 10: ...ity RAK3153 3203 230 208 volt line cord connection kit RAK4157 4207 4307 230 208 volt universal power supply kit RAK5157 5207 5307 265 volt universal power supply kit 230 208 volt Line cord connected units LCDI Power Connection Kit RAK3153 RAK3203 RAK3303 Heater KW 2 55 2 09 3 45 2 82 5 00 4 09 Watts 2 550 2 090 3 450 2 820 5 000 4 090 BTUH 8 600 7 100 11 700 9 600 17 000 13 900 Amps 11 6 10 6 15 ...

Page 11: ...50 13 400 6 400 6 200 8 400 8 200 10 900 10 700 13 800 13 800 COP 3 6 3 6 3 6 3 6 3 4 3 4 3 2 3 2 3 7 3 7 3 6 3 6 3 4 3 4 3 2 3 2 Watts 520 505 695 675 950 925 1 275 1 245 505 490 685 670 940 920 1 265 1 235 Amps 2 4 2 6 3 2 3 5 4 3 4 7 5 8 6 3 2 4 2 5 3 2 3 4 4 3 4 7 5 7 6 2 Weight Net Ship 102 117 105 120 113 128 123 138 108 122 113 128 118 133 127 142 Sound Transmission Class STC 29 29 29 29 29...

Page 12: ...Solenoids Circuit Boards Auxiliary Controls Thermistors Freeze Sentinel Frost Controls ICR Pump Capacitors Varistors and Indoor Blower Bearing if any of these parts should fail due to a defect in materials or workmanship During this additional four year limited warranty you will be responsible for any labor and related service costs See written warranty for details The Zoneline chassis is identifi...

Reviews: